Laserfiche WebLink
6. PIPING SUMP TESTING <br /> Test Method Developed By: ❑ Sump Manufacturer ® Industry Standard ❑Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑Pressure ❑Vacuum ®Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used: Incon TS-STs sump Test system Equipment Resolution: +/-0.002" <br /> Diesel <br /> Sutnp Diameter: 42" <br /> Sump Depth: 60" <br /> ISump Material: Fiberglass <br /> Height from Tank Top to Top of 2401 <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest <br /> 56" <br /> Electrical Penetration: <br /> Condition of sump prior to testing: Good <br /> Portion of Sump Tested' 4"Above Pen. <br /> Does turbine shut down when <br /> sump sensor detects liquid(both ❑Yes❑No ®NA ❑Yes❑No ®NA ❑Yes❑No®NA ❑Yes❑No U NA i <br /> roduct and water)?* <br /> Turbine shutdown response time N/A <br /> Is system programmed for fail-safe ❑Yes❑No U NA ❑Yes❑No U NA ❑Yes❑No®NA ❑Yes❑No U NA <br /> shutdown?* <br /> Was fail-safe verified to be ❑yes❑No ®NA ❑Yes❑No ®NA ❑Yes❑No®NA ❑Yes❑No ®NA <br /> o erational?* <br /> Wait time between applying <br /> pressure/vacuum/waterand starting 30 minutes <br /> test: <br /> Test Start Time: 08:59 AM <br /> Initial Reading(RI): 5.6109 <br /> Test End Time: 09:14 AM <br /> Final Reading(RF): 5.4461 <br /> Test Duration: 15 min. <br /> Change in Reading(RF-RI): -0.1648 <br /> Pass/Fail Threshold or Criteria: +/-0.002" <br /> Test Result: Fail <br /> Was sensor removed for testing? Yes <br /> Was sensor properly replaced and yes <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing, and reconmrendedfolloiv-up for failed tests) <br /> Sensor functionality was not confirmed.This procedure is not part of the Secondary Containment Testing scope of work. <br /> Sump is failing below electricals at penetrations. Sump not tested above electricals. <br /> f <br /> i <br /> I <br /> i <br /> ' If the entire depth of the sump is not tested,specify how much was tested. If the answer to any of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire sump must be tested. (See SWRCB LG-160) <br />