Laserfiche WebLink
6. PIPING SUMP TESTING <br /> Test Method Developed By: ❑ Sump Manufacturer ® Industry Standard ❑Professional Engineer <br /> ❑ Other(Specify) <br /> Test Method Used: ❑Pressure ❑Vacuum ®Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used: Incon TS-STS Sump Test System Equipment Resolution: +/-0.002" <br /> Diesel <br /> Sump Diameter: 421 <br /> Sump Depth: 60" <br /> Sump Material: Fiberglass <br /> Height from Tank Top to Top of 24" <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 56" <br /> Electrical Penetration: <br /> Condition of sump prior to testing: Good <br /> Portion of Sump Tested' 4"Above Pen. <br /> Does turbine shut down when <br /> sump sensor detects liquid(both ❑Yes❑No U NA ❑Yes❑No ®NA ❑Yes❑No®NA ❑Yes❑No ®NA <br /> product and water)?" <br /> Turbine shutdown response time N/A i <br /> Is system programmed for fail-safe <br /> shutdown?* O Yes❑No U NA ❑Yes❑No U NA ❑Yes❑No®NA ❑Yes❑No U NA <br /> Was fail-safe verified to be ❑Yesp No U NA ❑Yes❑No U NA ❑Yes❑No®NA ❑Yes❑No U NA t <br /> o erational?" <br /> I <br /> Wait tithe between applying i <br /> pressure/vacuum/water and starting 30 minutes <br /> test: <br /> Test Start Time: 08:59 AM <br /> Initial Reading(R): 5.6109 <br /> Test End Time: 09:14 AM <br /> Final Reading(RF): 5.4461 <br /> Test Duration: 15 min. <br /> Change in Reading(RF-Ri): -0.1648 J <br /> Pass/Fail Threshold or Criteria: +/-0.002" <br /> Test Result: Fail <br /> t <br /> Was sensor removed for testing? Yes <br /> Was sensor properly replaced and Yes <br /> verified functional after testi» ? <br /> Comments—(include information on repairs made prior to testing,and recommended follow-up for failed tests) <br /> Sensor functionality was not confirmed.This procedure is not part of the Secondary Containment Testing scope of work. <br /> Sump is failing below electricals at penetrations. Sump not tested above electricals. <br /> t <br /> i <br /> i <br /> 1 <br /> j <br /> ' If the entire depth of the sump is not tested,specify how much was tested. If the answer to any of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire sump must be tested. (See SWRCB LG-160) <br />