e)i IIs ale has t/4ec(0 �" `1"x.5 35D W4 a VeeCkt'- L I <br />In -Station Diagnostic (ISD) equipment is designed to monitor the collection and containment of vapors by vapor <br />recovery equipment. Using the existing Veeder-Root (V -R) TLS console platform, sensor inputs an dispenser fuel <br />meter inputs, the ISD software continuously monitors the vapor recovery equipment, maintains test records, <br />provides test reports, generates alarms following test/equipment failures, and finally, shuts down the site upon the <br />occurrence of designated alarms. <br />This manual provides instructions to install, setup, and operate the special components of the Veeder-Root ISD <br />system that are not covered in existing documentation shipped with other non -ISD specific V -R equipment (e.g. <br />Mag probes, line leak detection, etc.). The ISD feature is an option for the TLS console platform, and as such, <br />many of the installation/setup/operation instructions for non -ISD specific tasks (e.g., line leak detection) are <br />covered in TLS-3XX supplied literature. <br />WARNING! Revision or.reprogramming of the TLS --may require -notification -of the local Certified <br />Unified Program Agency (CUPA). <br />Site Requirements <br />Below are the requirements for all vapor recovery systems except where noted. <br />• V -R TLS-350R/EMC w/BIR, TLS -350 Plus/EMC Enhanced, TLS-350/EMC and Red Jacket ProMax consoles <br />with ECPUII - install as per TLS-3XX Site Prep manual, setup following instructions in TLS-3XX System Setup <br />Manual <br />• A flash memory board (NVMEM2) for ISD software storage - installed on the ECPUII board in place of the <br />console's 1/2 Meg RAM board - install as per TLS -350 Series Board and Software Replacement Manual, no <br />setup required. <br />• A RS -232 module is required for RS -232 access to ISD reports - install as per instructions shipped with <br />module, setup following instructions in this manual. <br />• An output relay is required (either 4 -Output Relay module, 1/0 Combination module) to shut down each <br />Submersible Turbine Pump (STP) upon activation of certain ISD alarms (these alarms can also be assigned in <br />Line Leak Disable setup to shut down the STP if Line Leak detection feature is installed) - install as per <br />instructions shipped with module or line leak system, setup ISD shut down alarms either using output relays or <br />line leak system following instructions in this manual. <br />• Dispenser Interface module (DIM) for the type of dispensers installed - install as per installation manual shipped <br />with device, setup following instructions in DIM manual and TLS-3XX Setup Manual. Note: the DIM supplies <br />flow meter event inputs needed for ISD analysis. <br />• One V -R Mag probe in each of the gasoline tanks being monitored - install as per installation manual shipped <br />with device, setup following instructions in TLS-3XX Setup Manual <br />• Smart Sensor module is required to monitor Air Flow Meters and Vapor Pressure Sensor (up to 8 devices per <br />module, or 7 if customer is using SmartSensor module / embedded pressure). Install and connect following <br />instructions in the Air Flow Meter and Vapor Pressure Sensor installation Guides. <br />• Air Flow Meters (one for each dispenser) - install as per ISD Flow Meter installation manual shipped with meter, <br />setup following instructions in this manual. <br />• -Vapor Pressure Sensor (one per site) - install as per ISD Pressure Sensor installation manual shipped with <br />sensor, setup following instructions in this manual. <br />• To achieve CP -201 false alarm performance standards for ISD reporting, the vapor recovery system leak rate <br />should be at or below 2.88 CFH at 2 inches water column. <br />1-1 <br />