Laserfiche WebLink
-May 28 04 01 : 33a MiWatten (206533-2650 p. 6 <br /> AlItech #2kO52704 <br /> 3.8 <br /> E. 0 <br /> > <br /> -3.8 - <br /> o 4- <br /> Sample Time (in Hrs.) <br /> Client/Operator Data Tank and Test Parameters <br /> Client: California Stop Tank Identification: T3 Diesel <br /> Address: 2224 Manthey Rd. Product Type: Diesel <br /> City, St: Stockton CA 95206 Tank Capacity: 11627 Gal. <br /> Telephone: 209-462-7621 Product Level: 66 in, <br /> Water in Tank: 0 <br /> Contractor: Alltech Water Level ATB: 0 in. <br /> Address: 17759 Buttercup Circle Tank Material: FRP <br /> City, St: Sonora CA 95370 Tank Manufacturer: Unknown <br /> Telephone: 209-532-7320 Load Cell SIN: 246800001300 <br /> Probe S/N: 28 <br /> Operator: Mike Dotten Probe Length: 89.00 Inches <br /> Certification#: 2002002 Test Duration (min): 2.160 Hours <br /> Expiration Date:1.28.05 Sample Time: 1.3 Hours <br /> Product SGU: 0.83 <br /> Tank 3 Leak Rate G/H: -0,015 <br /> Tank Address: 2224 Manthey Rd. <br /> City, St: Stockton CA <br />