Laserfiche WebLink
0 CqECEIVED <br /> a <br /> 1115000 Field Test ApparatusENVIRONMENTA6e 1 of 1 <br /> Line Leak Detector Test HEALTH DEPARTMENT <br /> Work Order: 2314893 Date: 1/14/2014 <br /> Site Name/ID: CHEVRON 201761 /201761 <br /> Address: 1103 S.MAIN ST. PERMIT NUMB. N-3315 <br /> City: MANTECA State: CA Zip: 95337 <br /> Tank ID T1 Supreme T3 Regular 1 <br /> Product SUPREME REGULAR <br /> Product Line 1 1 <br /> Tested From 9 9 <br /> Existing/New Existing Existing <br /> Mechanical/Electronic Electronic Electronic <br /> Manufacturer/Model Veeder Root PLILD Veeder Root PLLD <br /> Serial No. 016543 015618 <br /> Pump Operating Pressure(psi) 30.00 30.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 <br /> Holding PSI <br /> N/A for Electronic Lo's <br /> Resiliency(ml) <br /> NIA for Electronic Lo's <br /> Watering PSI <br /> N/A for Electronic Lo's <br /> pening Time(sec) <br /> NIA for Electronic Lo's <br /> est Results Pass Pass <br /> Technician Comments: <br /> Technician Name: Jarrod Cooke Certification#: 1352 <br /> Technician Signature:' Expire Date: 2/10/2015 <br /> Environmental Compliance for Petroleum Systems <br /> 0 2014 Tanknology Inc.,Austin,Tx. All rights reserved. tanknology.com <br />