Laserfiche WebLink
SWRCB,January 2002 Page I of I <br /> 9. SPILUOVERFILL CONTAINMENT BOXES <br /> Facility is Not Equipped With Spill/Overfill Containment Boxes r <br /> Spill/Overfill Containment Boxes are Present,but were Not Tested ' <br /> Test Method Developed By: F Spill Bucket Manufacturer 1āœ“ Industry Standard T Professional Engineer <br /> I— Other(Specify): <br /> Test Method Used By: r Pressure Io Vacuum r Hydrostatic <br /> r Other(Specify): <br /> Test Equipment Used:VACUUM TEST Equipment Resolution:0.1 gph <br /> SpiJI Box#Tank 11 Spill Bax#Tanl.T2 Spill Box Tank T3 <br /> Supreme SUPREME Regular 2 REGULAR`.- Regular 1 RECrtiA`R <br /> Fill 1 Direct Grade Filli Direct Grade Fill] Dnct=Grade: ill BOX <br /> ]eve l in:containment level to containment level in containment <br /> sump sump ;sumpdd <br /> Bucket Diameter: 12.00 12.00 12.00 <br /> Bucket Depth: 14.00 14.00 14.00 <br /> Wait time between applying <br /> pressure/vacuum/water and 7 min 5 min 5 min min <br /> starting test <br /> Test Start Time: 09:06:00 09:10:00 09:14:00 <br /> Initial Reading(Rt): 30.00 in.H2O 30.00 in.H2O 30.00 in.H2O <br /> Test End Time: 09:07:00 09:11:00 09:15:00 <br /> Final Reading(RF): 30.00 in.H2O 30.00 in.H2O 30.00 in.H2O <br /> Test Duration: 1 min 1 min I min <br /> Change in Reading(RF-R1): 0.00 in.1-120 0.00 in.H2O 0.00 in.H2O <br /> Pass/Fail Threshold or Criteria: +/-4.00 +/-4.00 +/-4.00 +/- <br /> Test iiasult: Pass Fars. Pass <br /> Comments-(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> WO:2314893 <br />