Laserfiche WebLink
Page 1 of 1 <br /> SPILL/OVERFILL CONTAINMENT BOXES <br /> Facility is Not Equipped With Fill Riser Containment Sumps <br /> Fill Riser Containment Sumps are Present, but were Not Tested <br /> Test Method Developed By: r Spill Bucket ManufacturerC Industry Standard r Professional Engineer <br /> r Other (Specify): <br /> Test Method Used By: r Pressure ro vacuum r Hydrostatic <br /> Other (Specify): <br /> Test Equipment Used: Equipment Resolution: ph� <br /> Spill Box Spill Box,# Spill Box# <br /> Tank 1� Ssxpre�xieSUPREME TaniC T ,Regula 2 REGULAR Tank T3 Regular 1 RULAR Spi(I_Box # <br /> 'Fill btrect Fill :Pirect ' Fill - Direct"; <br /> Bucket Diameter: 12.00 12.00 12.00 <br /> Bucket Depth: 13.00 13.75 12.75 <br /> Wait time between <br /> applying 1 min 1 min 1 min min <br /> pressure/vacuum/water <br /> and starting test <br /> Test Start Time: 10:07:00 10:03:00 09:59:00 <br /> Initial Reading(R,): 30.00 PSI 30.00 PSI 30.00 PSI <br /> Test End Time: 10:08:00 10:04:00 10:00:00 <br /> Final Reading otFi: 30.00 PSI 27.00 PSI 29.00 PSI <br /> Test Duration: 1 min 1 min 1 m i n <br /> Change in Reading mom, 0.00 PSI -3.00 PSI -1.00 PSI <br /> Pass/Fail Threshold or <br /> +/ 0.00 +/- 3.00 +/ 1.00 <br /> Criteria: +/ <br /> Test Result:. ' �` Pass Baas ,. Pass <br /> Comments? (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> WO: 2308165 <br />