Laserfiche WebLink
I <br /> 3 [ <br /> 3 P <br /> 1115000 Field Test Apparatus <br /> gTanknoiogy Page 1 of 1 ; <br /> Line Leak Detector Test <br /> Work Order: 2308165 Date: 1/18/2013 <br /> Site Name/ID: CHEVRON 201761 /201761 <br /> Address: 1103 S. MAIN ST. PERMIT NUMB. N-3315 <br /> City: MANTECA State: CA Zip: 95337 <br /> Tank ID T1 Supreme T3 Regular 1 T3 Regular 1 <br /> Product SUPREME REGULAR REGULAR <br /> Product Line 1 1 1 <br /> I <br /> Tested From 9 9 9 <br /> Existing/New Existing Existing Existing <br /> Mechanical/Electronic Electronic Electronic Electronic <br /> Manufacturer/Model Veeder Root PLLD Veeder Root PLLD Veeder Root PLLD <br /> i <br /> Serial No. 016543 015618 015618 <br /> j Pump Operating Pressure(psi) 41.00 47.00 45.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 E <br /> Holding PSI 20.00 19.00 19.00 <br /> 'NIA for Electronic LD's <br /> I Resiliency(ml) <br /> N A for Electronic LD's <br /> Metering PSI <br /> NIA for Electronic LD's <br /> Opening Time(sec) <br /> NMA for Electronic LD's <br /> Test Results Pass Pass Pass <br /> Technician Comments:had to test 87 PLLD twice per inspector to insure both turbines shutdown <br /> i <br /> E <br /> I <br /> Technician Name: Steven Willems Certification : 59437 <br /> �J9 Expire Date: 8/29/2013 <br /> Technician Signature: 2:14:20PM <br /> Environmental Compliance for Petroleum Systems <br /> ©2010 Tanknology Inc.,Austin,TX. All rights reserved. tanknology.com <br />