Laserfiche WebLink
SWRCB,January 2002 Page of <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: x Tank Manufacturer ❑Industry Standard ❑Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure x Vacuum ❑Hydrostatic <br /> ❑Other(Sped) <br /> Test Equipment Used: Dwyer Manometer Equipment Resolution:+/-2% <br /> Tank# I Tank# Tank# Tank# <br /> Is Tank Exempt From Testing?' x Yes ❑No ❑Yes ❑No ❑Yes ❑No ❑Yes ❑No <br /> Tank Capacity: <br /> Tank Material: <br /> Tank Manufacturer: <br /> Product Stored: <br /> Wait time between applying <br /> pressure/vacuum/water and 30 min 30 min 30 min 30 min <br /> starting test: <br /> Test Start Time: <br /> Initial Reading(Ri): <br /> Test End Time: <br /> Final Reading(RF): <br /> Test Duration: 1 hour 1 hour 1 hour 1 hour <br /> Change in Reading(RF-R,): <br /> Pass/Fail Threshold or Criteria: No less than 1" No less than 1" No less than 1" No less than 1" <br /> Test Result: ❑ Pass ❑Fail ❑ Pass ❑Fail ❑ Pass ❑Fail ❑ Pass ❑Fail <br /> Was sensor removed for testing? x Yes ❑No ❑NA x Yes ❑No ❑NA x Yes ❑No [INA x Yes ❑No ❑NA <br /> Was sensor properly replaced and x Yes 11No 11NA x Yes ❑No ❑NA x Yes ❑No ElNA x Yes []No ❑NA <br /> verified functional after testing? <br /> Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> Annular space is wet <br /> ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23, Section 2637(a)(6)1 <br />