Laserfiche WebLink
STOCKTON SERVICE STATION• r • <br />808 N. UNION <br />STOCKTON, <br />PHONE0• 0. <br />.464.8349 <br />i•1 •VIA• <br />CUSTOMER: Tracy Truck Stop DATE: March 8, 2007 <br />LOCATION: 3940 N. Tracy Blvd. <br />CITY: Tracy STATE: CA ZIP: 95304 <br />TECHNICIAN: MIKE JONES <br />Submersible Pump Identification <br />Manufacturer Model Serial Number <br />Red Jacket 5 H.P. <br />Leak Detector Identification <br />Manufacturer Description Other Style Leak Detector <br />Vaporless 99LD 3000 <br />Diaphragm -type DIESEL T-4, EAST <br />Piston -type X <br />Leak Detector in Submersible Pump <br />Test at Dispenser <br />1. Operating Pump Pressure 29 psi (Purging Test System) <br />2. Gallons per hour rate 3 Gallon (Leak Test, Phase I) <br />3. Line pressure with pump shut off 25 psi (Leak Test Phase I) <br />4. Bleed -Back Test with pump off 300 ml (Bleed -back Test) <br />5. Step -through time to full flow 10 seconds (Step -through Time) <br />6. Leak detector stays in leak search position. (Leak Test Phase II) Yes X No <br />LEAK DETECTOR TEST <br />Note: Pass = Leak detector fits test protocol <br />Fall = Leak detector fails test protocol <br />Pass X <br />Fail <br />Form 890C <br />