Laserfiche WebLink
STOCKTON SERVICE STATION EQUIPMENT CO. INC. <br />808 N. UNION STREET <br />STOCKTON, CA 95205-4152 <br />PHONE 209.464.8333 FAX 209.464.8349 <br />LDT-890 LEAK DETECTOR TEST RECORD <br />CUSTOMER: Tracy Truck Stop DATE: March 13, 2007 <br />LOCATION: 3940 N. Tracy Blvd. <br />CITY: Tracy STATE: CA ZIP: 95304 <br />TECHNICIAN: MIKE JONES <br />Submersible Pump Identification <br />Manufacturer Model Serial Number <br />Red Jacket 1-1/2 H.P. <br />Leak Detector Identification <br />Manufacturer Description Other Style Leak Detector <br />Vaporless 99LD 2000 Serial #07031003 <br />Diaphragm -type UNLEAD SUPREME T-1.91 OCTANE <br />Piston -type X <br />Leak Detector in Submersible Pump <br />Test at Dispenser <br />1. Operating Pump Pressure 27 psi (Purging Test System) <br />2. Gallons per hour rate 3.0 Gallon (Leak Test, Phase 1) <br />3. Line pressure with pump shut off 27 psi (Leak Test Phase I) <br />4. Bleed -Back Test with pump off 175 wl ,Illeed-hacl. Tess) <br />5. Step -through time to full flow 8 seconds (Step -through Time) <br />6. Leak detector stays in leak search position. (Leak Test Phase II) Yes X No <br />LEAK DETECTOR TEST <br />Note: Pass = Leak detector fits test protocol <br />Fall = Leak detector fails test protocol <br />Pass X <br />Fail <br />Foran 890C <br />