Laserfiche WebLink
SWRCB,January 2002 Page of <br /> 9. SPILL/OVERFILL CONTAINMENT BOXES <br /> Facility is Not Equipped With Spill/Overfill Containment Boxes❑ <br /> Spill/Overfill Containment Boxes are Present,but were Not Tested❑ <br /> Test Method Developed By: ❑Spill Bucket Manufacturer ✓❑Industry Standard ❑Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: El Pressure ❑Vacuum ❑Hydrostatic <br /> ✓❑Other(Spec) Inches, 1 hr visual test <br /> Test Equipment Used:See attached testing procedures Equipment Resolution: Inches 1 hr--i{P5 <br /> Spill Box#87 Fill Spill Box#91 Fill Spill Box#87 Vapor Spill Box#91 Vapor <br /> Bucket Diameter: 12" 12" 12" 12" <br /> Bucket Depth: 14.5" 14.5" 16" 16" <br /> Wait time between applying <br /> pressure/vacuum/water and 15 minutes 15 minutes 15 minutes 15 minutes <br /> starting test: <br /> Test Start Time: 9:05am 9:05am 9:05am 9:05am <br /> Initial Reading(RI): 13.75 Inches,I hr Wsual test 13.5 leohes.,hr Wsua1— 14 Inches.I h,v..1— 14.25 n0se,I hr vis..l. <br /> Test End Time: 10:05am 10:05am 10:05am 10:05am <br /> Final Reading(RF): 13.75 laches,1 h,Ws.al lest 13.5 Inches,t h,-,al test 14 Inches.,h,visna teal 14.25 Inches.,h,W5..1. <br /> Test Duration: 1 Hr 1 Hr 1 Hr 1 Hr <br /> Change in Reading(RF-RI): 0 0 0 0 <br /> Pass/Fail Threshold or 0.002 0.002 0.002 0.002 <br /> Criteria: <br /> 7Cest;2esult,..,, L „ ®Pass [Fail ✓❑ ass;;:�i* i ❑✓,Pass <br /> []Fail, ✓ Pass <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> Direct Bury Buckets <br /> RECEIVED <br /> JUL 0 2 20 <br /> E VIROMMENTIAL HEALTH <br /> PERMIT/SERVIC'E <br />