Laserfiche WebLink
0 0 <br />SPILUOVERFILL CONTAINMENT BOXES <br />Facility is Not Equipped With Fill Riser Containment Sumps <br />Fill Riser Containment Sumps are Present, but were Not Tested i <br />Test Method Developed By: r Spill Bucket Manufacturer ro Industry Standard <br />r Other (Specify): <br />Test Method Used By: r Pressure C+" Vacuum <br />i" Other (Specify): <br />Test Equipment Used: VACUUM TEST Equipment Resolution: <br />Bucket Diameter. 12.00 12.00 <br />Bucket Depth: 13.75 14.00 <br />Wait time between applying 1 min 1 m i n <br />pressure/vacuumlwater and starting test <br />Test Start Time: <br />10:13:00 <br />10:08:00 <br />Initial Reading (R�: <br />30.00 in. H2O <br />30.00 in. H2O <br />Test End Time: <br />10:14:00 <br />10:09:00 <br />Final Reading (Rd: <br />30.00 in. H2O <br />30.00 in. H2O <br />Test Duration: <br />1 min <br />1 m i n <br />Change in Reading (R.R�: 1 0.00 in. H2O 1 0.00 in. H2O <br />min <br />Page 1 of 1 <br />t" Professional Engineer <br />f Hydrostatic <br />min <br />Pass/Fail Threshold or Criteria: I +/-4.00 1 +/-4.00 1 +/- I +/- <br />Comments ? (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />NIFLigMI� R11 <br />