Veeder-Root Line Leak ApplicaW Guide ` <br /> Precision Testing Frequencies <br /> On-Demand (D) <br /> Testing can be initiated manually through the TLS Console or by programming a date and time into memory. <br /> Auto (A) <br /> Tests will run repetitively until a passing test is achieved.Once a passing test is achieved,testing will stop and recommence six <br /> months from the date of the last passing test. <br /> Monthly (M) <br /> Tests will run repetitively until a passing test is achieved.Once a passing test is achieved,testing will stop and recommence the <br /> first calendar day of the next month. <br /> Repetitive (R) <br /> Tests will run repetitively according to pre-programmed time intervals. <br /> Refer to the matrix below to determine which precision testing option best meets your needs: <br /> • • e e <br /> ULTIMATE TESTING D,M,R D,A,R <br /> RISK MANAGEMENT D,M,R D,A <br /> BASE COMPLIANCE NONE D,A <br /> WPLLD Accessories & Spare Parts for Existing TLS-350 Series Consoles <br /> The following WPLLD accessories and spare parts are available: <br /> 330020-290 WIRELESS REPLACEMENT TRANSDUCER FOR RED JACKET PUMPS <br /> 330020-291 WIRELESS REPLACEMENT TRANSDUCER FOR FE PETRO PUMPS <br /> 330773-001 SWIFTCHECK VALVE FOR WPLLD <br /> 330841-001 WPLLD CONTROLLER MODULE <br /> 330874-001 WPLLD AC INTERFACE MODULE <br /> 330883-001 WPLLD COMMUNICATIONS MODULE <br /> 331689-001 NON—VENTED SWIFTCHECK <br /> 9 <br />