Laserfiche WebLink
c <br /> Veeder-Root Line Leak ApAtion Guide 0 <br /> 4. Locate red switch bank labeled S1 on the CPT's Controller CPU board,and verify that dip switch 2 is set to the Closed <br /> position(to enable the PLLD precision line leak function),and dip switch 8 is set to the Open position (to disable the CPT's <br /> line leak function). <br /> 5. Verify that the Rotary Pressure Dial, also on the CPT's Controller CPU board, is set to either the 2(24 psi),3(27 psi),4(30 <br /> psi), 5(33 psi),or 6(36 psi)position. <br /> `\\ plld/cptplld.epe <br /> O i►�._ _ Tr1 L -1_____________ <br /> LT LT <br /> tr• r- <br /> -00 I i Oi ® PLLD <br /> -'` o l i �• transducer <br /> ii PLLD o Only <br /> transducer 0 UP <br /> in SwiftCheck <br /> 10 O Valve ;O <br /> _ SpikeCheck <br /> O --- Valve Assy. <br /> O <br /> Functional -_ <br /> Element <br /> Red Jacket Standard CPT Red Jacket Quantum CPT <br /> Transducer Installation -Red Jacket Big-Flo and Maxxum Pumps <br /> BIG-FLO PUMPS <br /> 1. You will need to install a reducing tee(customer supplied)in either of the 3-inch discharge ports of the pump with the 2- <br /> inch opening facing up. If you have the room, it may be easier to install this tee between the Pressurstat kit and the unused <br /> port instead of in the discharge line(as shown in the figure below).Alternatively,the PLLD transducer can be installed in <br /> the leak detector port of a Big-Flo leak detector if it is already present in the line(as shown in the figure below). <br /> 2. Install the Red Jacket Big-Flo Pressurstat Kit(Red Jacket part number 144-314-5)following the instructions with the kit. <br /> 3. Thread the PLLD transducer into the 2-inch opening of the tee. <br /> + IMPORTANT!Seal any pipe threads using a UL-classified,nontoxic pipe sealant suitable for the fuel involved. <br /> 4. Verify that the console has Version x19 or later software. <br /> Junction box <br /> OPTIONAL INSTALLATION EXAMPLE (customer supplied) <br /> c P 0 <br /> 3/4"NPT Union, <br /> 3/4"NPT nipples, PLLD transducer <br /> reducing nippleSeal-off,epoxy seal per NFPA <br /> / 3"discharge line <br /> (customer supplied) / (to dispensers) spec(customer supplied) <br /> tG conduit to console <br /> '0 (customer supplied) <br /> PLLD transducer in 2"port of <br /> Big-Flo Leak Detector(customer <br /> �upplied) <br /> Red Jacket Big-Flo <br /> 3"x 3"90 degree elbow <br /> Red Jacket Bi Flo Pressurstat kit- (customer supplied) <br /> Pressurstat kit- 2"x 2"x 3"reducing tee P/N 144-314-5 \ <br /> P/N 144-314-5 and 3"NPT nipple (customer supplied) 3"discharge line(to dispensers) <br /> (customer supplied) (customer supplied) <br /> pIl.igflo7.eps <br /> 11 <br />