Laserfiche WebLink
0 0 <br /> 6. Contact Ray von Flue(468-9848)to arrange the following inspections(a 48-hour notice <br /> is required): <br /> a. Twenty-four hour lake test(or equivalent)on the under dispenser containment. <br /> 7. An"Underground Storage Tank Certification of Installation/Modification" form shall be <br /> submitted by the owner or the owners'agent [pursuant to(CCR)2635(d)] before this <br /> upgrade will be considered complete by EHD. <br /> 8. Permit expires July 29,2008. <br /> Ray von Flue,REHS <br /> Senior Registered Environmental Health Specialist <br />