Laserfiche WebLink
SWRCB, January 2002 <br />Page 2 <br />9. SPILL/OVERFILL <br />CONTAINMENT BOXES <br />Facility is Not Equipped With Spill/Overfill Containment Boxes: <br />Spill/Overfill Containment Boxes are Present, but were Not Tested: <br />Test Method Developed By: <br />❑ Spill Bucket Manufacturer <br />Industry Standard <br />❑ Professional Engineer <br />Other (Specify) TECH <br />Test Method Used: <br />II Pressure <br />F Vacuum <br />Hydrostatic <br />El Other (Sped) <br />Test Equipment Used: <br />Equipment Resolution: <br />EMME <br />Spill Box # DSL-E Spill Box # DSL-W Spill Box # <br />87 Spill Box # W .OIL <br />Bucket Diameter: <br />12X12 <br />12X12 12X12 <br />12X12 <br />Bucket Depth: <br />24 <br />24 24 <br />24 <br />Wait time between applying <br />pressure/vacuum/water and <br />5MIN <br />5MIN 5MIN <br />5MIN <br />starting test: <br />Test Start Time: <br />0930 <br />0930 0930 <br />0930 <br />Initial Reading (RI ): <br />18 <br />18 18 <br />18 <br />Test End Time: <br />1030 <br />1030 1030 <br />1030 <br />Final Reading (RF ): <br />18 <br />18 18 <br />18 <br />Test Duration: <br />1HR <br />1HR 1HR <br />1HR <br />Change in Reading (R F- Rt) <br />0 <br />0 0 <br />0 <br />Pass/Fail Threshold or <br />Criteria: <br />MEE <br />Comments - (include inforanation on repairs made prior to testing, and recommended follow-up for fciile(I tents) <br />TIGHTEN BOLTS ON DSL-EAST <br />SPILL BUCKET. <br />