Laserfiche WebLink
VM1 I <br /> Vaporless Manufacturing, Inc. <br /> Quality Petroleum Equipment <br /> Solutions for Over 20 Years <br /> LDT-890 Test Form&VMI Warranty Checklist <br /> October 1 2006 <br /> Test Information <br /> Date: 10/22/08 Test Company: EPIC Compliance Systems, Inc. <br /> Telephone: 916-386-3767 Contact : Steve <br /> Site I.D: Teichert&Sons Address: 120 Frank West Circle <br /> City: Stockton State: CA Zip: 95206 <br /> Type of Test Equipment: LDT-UQ <br /> Submersible PumD Identification. <br /> MFG: RED JACKET Model No: p500H3-2K Serial No: 7598 <br /> Leak Detector Identification <br /> MFG: Veeder Root Model No: PLLD (8484) Serial No: _1-14Q-12___ <br /> Replacement Leak Detector Identification <br /> MFG: Model No: Serial No: <br /> Line Conditions <br /> 1.Type of Pipe: FG 2.Diameter of Pipe: 3" 3.Length of Pipe: 40' <br /> 4.Burial Depth of Leak Detector: 3' 5.Kind of Fuel: Diesel 6.Date of Last Line Test: - <br /> Test Conditions <br /> 1.Operating Pump Pressure: 37 2.Gallon per hour test rate: 3 @ 10 psi <br /> 3.Static Line Pressure(Pump Off): 12- 4.Bleedback Test(Pump Off): 55 mi. <br /> 5.Step-through time to full flowWAseconds(0 psi.to full pump pressure,no leak) <br /> 6.Leak detector stays in Leak Search Position with a 3 GPH leak-Yes: N/A PASS No: FAIL <br /> 7.Was the leak detector adjusted—Yes: No: X <br /> PLLD detected leak rate and disabled pumping Pass <br /> Symptoms <br /> 1.Won't find 3 GPH leak: 2.Stays in Slow Flow: <br /> 3.Other: <br /> If This Unit Is Returned Under Warranty Please Complete The Following <br /> Vaporless RGA#: Return By(Company): <br /> Telephone: Contact: <br /> Customer Control#: Address: <br /> City: State: Zip: <br /> (See Website-www.vaporiess.com -Technical Bulletin 032805) <br />