Laserfiche WebLink
ANNUAL4SPILL CONTAINER TE* REPORT <br />TEST DATE: September 13, 2012 <br />A7. FACILITY <br />A2. OWNER <br />Name <br />Teichert Mobile Equipment <br />San Joaquin County Environmental Health <br />Name <br />Teichert Construction <br />Address <br />120 Frank Circle, Stockton, CA 95206 <br />1868 E. Hazelton Avenue, Stockton, CA 95202 <br />Address <br />P.O. Box 15002, Sacramento, CA 95851 <br />Phone # <br />916-366-8631 <br />September 5, 2012 <br />Phone # <br />916-386-3767 <br />Contact <br />Steve Schamaun <br />Stacy Rivera <br />Contact <br />Steve Schamaun <br />A3. C U P A <br />A4. TESTING CONTRACTOR <br />Name <br />San Joaquin County Environmental Health <br />Name <br />Walton Engineering, Inc. <br />Address <br />1868 E. Hazelton Avenue, Stockton, CA 95202 <br />2 <br />Address <br />P.O. Box 1025, W. Sacramento, CA 95691 <br />Notified <br />September 5, 2012 <br />Product contained <br />Lic # <br />617238 A, B, Haz <br />Inspector <br />Stacy Rivera <br />Contact <br />Dulcinea Coven <br />Phone # <br />209-468-8257 <br />Phone # <br />916-373-1166 <br />K. SPILL CONTAINER TEST RESULTS <br />Measuring Equipment Used: Caldwell System 2001 / Walton Engineering (Level Change Indicator) <br />Tank Number <br />1 <br />Diesel_? <br />2 <br />3 <br />4 <br />Product contained <br />Gasoline - 87 <br />Waste oil <br />Diesel 2 <br />Spill container capacity (US gallons) <br />5 <br />5 <br />5 <br />Spill container manufacturer <br />CNI <br />CNI <br />CNI <br />Spill container_ depth (inches) <br />16.00 <br />15.50 <br />_ <br />15.50 <br />Is the spill container located in a sump? <br />Yes <br />Yes <br />Yes <br />Does sump have a liquid sensor installed? <br />No <br />No <br />Yes <br />Condition of spill container prior to testing <br />Dry <br />Dry <br />Dry <br />Portion of spill container tested <br />Entire <br />Entire <br />Entire <br />Depth of water level from bottom (inches)14.50 <br />14.00 <br />14.00 <br />Wait time for water level to stabilize0:10 _(hr:min) <br />0:10 <br />0:10 <br />Test start time <br />12:04 <br />10:36 <br />14:00 <br />Test end time <br />12:34 <br />11:06 <br />14:30 <br />Test duration (hr:min) <br />0:30 <br />0:30 <br />0:30 <br />Change in water level (t 0.000 inches) <br />0.000 <br />0.001 <br />_ <br />0.003 <br />Pass/Fail threshold (0.005 inches /'/z Hr.) <br />0.005 <br />0.005 <br />TEST RESULT <br />PASS <br />PASS <br />L. COMMENTS: <br />Replaced the fill cap on the 87 product. <br />0.005 <br />PASS <br />Signature: <br />WALTON <br />ENGINEERING, INC. <br />Technician: Curtis Carpenter 1837258 8020679 Date: September 13, 201. <br />