Laserfiche WebLink
M <br />I. MECHANICAL LINE LEAK DETECTOR TEST RESULTS <br />Test Equipment Used: Vaporless VMI LDT-890 <br />LINE LEAW)ETECTOR (LLD) TE!V REPORT <br />TEST DATE: <br />September 8, 2011 <br />Al. FACILITY <br />1 <br />A2. OWNER <br />Name <br />Teichert Mobile Equipment <br />Diesel #1 - Sump #1 <br />Name Teichert Construction <br />Address <br />120 Frank Circle, Stockton, CA 95206 <br />Leak Detector Type <br />Address 8833 Kiefer Blvd., Sacramento, CA 95826 <br />Phone # <br />916-366-8631 <br />Phone # 916-386-3767 <br />Contact <br />Steve Schamaun <br />0848480-001 <br />Contact Steve Schamaun <br />Serial number <br />114012 <br />270880 <br />1196085 <br />A3. C U P A <br />Functional Element Holding (psi) <br />31 <br />A4. TESTING CONTRACTOR <br />Name <br />San Joaquin County Environmental Health <br />Resiliency (ml) <br />Name Walton Engineering, Inc. <br />Address <br />600 E. Main Street, Stockton, CA 95202 <br />Address P.O. Box 1025, W. Sacramento, CA 95691 <br />Notified <br />September 1 , 2011 <br />3.00 <br />Lic # 617238 A, B, Haz <br />Inspector <br />Stacy Rivera <br />35 <br />Contact Dulcinea Covan <br />Phone # <br />209-468-8257 <br />0 <br />Phone # 916-373-1166 <br />I. MECHANICAL LINE LEAK DETECTOR TEST RESULTS <br />Test Equipment Used: Vaporless VMI LDT-890 <br />Tank number <br />1 <br />1 <br />2 <br />Product contained <br />Diesel #1 - Sump #1 <br />Diesel #2 - Sump #2 <br />Gasoline - 87 <br />Leak Detector Type <br />ELLD <br />ELLD <br />ELLD <br />Leak detector make/model <br />0848480-001 <br />0848480-001 <br />0848480-001 <br />Serial number <br />114012 <br />270880 <br />1196085 <br />Functional Element Holding (psi) <br />31 <br />35 <br />32 <br />Resiliency (ml) <br />100 <br />90 <br />85 <br />Test leak rate (gph) <br />3.00 <br />3.00 <br />3.00 <br />Pump pressure (psi) <br />31 <br />35 <br />32 <br />Metering pressure (psi) <br />0 <br />0 <br />0 <br />Pressure Restriction Reduction (psi) <br />31 <br />35 <br />32 <br />Length of Restriction Test (seconds) <br />0 <br />0 <br />0 <br />Full Flow Opening time (seconds) <br />0 <br />0 <br />0 <br />TEST RESULT <br />PASS <br />PASS <br />PASS <br />Tank number <br />Product contained <br />Leak Detector Type <br />Leak detector make/model <br />Serial number <br />Functional Element Holding (psi) <br />Resiliency (ml) <br />Test leak rate (gph) <br />Pump pressure (psi) <br />Metering pressure (psi) <br />Pressure Restriction Reduction (psi) <br />Length of Restriction Test (seconds) <br />Full Flow Opening time (seconds) <br />TEST RESULT <br />J. COMMENTS: <br />I <br />WALTON. <br />Signature: C O --� ENGINEERING. INC <br />Technician: Gerardo Guzman 1835394 5242481 -UT Date: September 8, 2011 <br />