Monitoring System Certification - "0 <br />of 3 <br />1:1 <br />Site Address: 1330 E. Yosemite @ Highway 99 Date of Testing/Servicing <br />D. Results of Testing / Servicing <br />Software Version Installed- 0 <br />thn fnnnwina rhr oltlict^ <br />02/26/02 <br />® Yes <br />❑ No* <br />Is the audible alarm operational? <br />® Yes <br />❑ No* <br />Is the visual alarm operational? <br />® Yes <br />❑ No* <br />Were all sensors visually inspected, functionally tested, and confirmed operational? <br />® Yes <br />❑ No* <br />Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will <br />not interfere with their proper operation? <br />❑ Yes <br />❑ No* <br />If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) <br />99 N/A <br />operational? <br />® Yes <br />❑ No* <br />For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment <br />❑ N/A <br />monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate <br />positive shut -down? (Check all that apply) ❑ Sump/Trench Sensors; ❑ Dispenser Containment Sensors. <br />Did you confirm positive shut -down due to leaks and sensor failure/disconnection? ❑ Yes ❑ No <br />❑ Yes <br />❑ No* <br />For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no <br />® N/A <br />mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank <br />fill point(s) and operating properly? If so, at what percent of tank capacity does the alarm trigger? 0 % <br />❑ Yes* <br />IN No <br />Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced <br />and list the manufacturer name and model for all replacement parts in Section E, below. <br />® Yes* <br />❑ No <br />Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) <br />❑ Product; ❑ Water. If yes, describe causes in Section E, below. <br />® Yes <br />❑ No* <br />Was monitoring system set-up reviewed to ensure proper settings? Attach set-up reports, if applicable <br />❑Yes <br />®No* <br />Is all monitoring equipment operational per manufacturer's specifications? <br />* In Section E below, describe how and when these deficiencies were or will be corrected. <br />E. Comments: Need to movereg, prem and diesel fill sump sensor to lowest point in sump. Diesel Sump <br />sensor needs to be moved to other side of sump. Dispenser pan sensor on #9-10 bad. <br />3/13/02 - Removed water from fill sumps. Left barrel at site. Relocated all three fill sump <br />sensors to lowest point in sump and relocated prem and diesel stp sump sensor to correct <br />location in sump. Replaced dispenser pan on #9-10, all tested O.K. <br />Premium and diesel share the annular sensor <br />