My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2015-2018
Environmental Health - Public
>
EHD Program Facility Records by Street Name
>
Y
>
YOSEMITE
>
1234
>
2300 - Underground Storage Tank Program
>
PR0516248
>
COMPLIANCE INFO_2015-2018
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
10/13/2023 11:28:32 AM
Creation date
6/3/2020 10:00:28 AM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2015-2018
RECORD_ID
PR0516248
PE
2361
FACILITY_ID
FA0012532
FACILITY_NAME
CHEVRON STATION #209167
STREET_NUMBER
1234
Direction
E
STREET_NAME
YOSEMITE
STREET_TYPE
AVE
City
MANTECA
Zip
95336
APN
22120016
CURRENT_STATUS
01
SITE_LOCATION
1234 E YOSEMITE AVE
P_LOCATION
04
P_DISTRICT
005
QC Status
Approved
Scanner
SJGOV\rtan
Supplemental fields
FilePath
\MIGRATIONS\UST\UST_2361_PR0516248_1234 E YOSEMITE_2015-2018.tif
Tags
EHD - Public
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
340
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
4. TANK ANNULAR TESTING <br /> Test Method Developed By: ❑Tank Manufacturer ✓❑Industry Standard ❑Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure ❑✓ vacuum ❑Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used:See attached testing procedures Equipment Resolution: inHg <br /> MENEM Tank#87 Tank# 91 Tank# Tank# <br /> Is Tank Exempt From Testing?' ❑Yes ❑No ❑Yes No ❑Yes [:]No ❑Yes ❑No <br /> Tank Capacity: <br /> Tank Material: Fiberglass Fiberglass <br /> Tank Manufacturer: <br /> Product Stored: 87 Gas 91 Gas <br /> Wait time between applying <br /> pressure/vacuum/water and 15 minutes 15 minutes <br /> starting test: <br /> Test Start Time: 9:16am 8:48am <br /> Initial Reading(RI): 10 inHg 10 inHg inHg inHg <br /> Test End Time: 10:16am 9:48am <br /> Final Reading(RF): 10 inHg 10 inHg inHg inHg <br /> Test Duration: 1 hour 1 hour 1 hour <br /> Change in Reading(RF-R,): 0 0 <br /> Pass/Fail Threshold or Criteria: 0 0 <br /> Test Result: ❑✓ Pass ❑Fail ❑✓ Pass ❑Fail ❑Pass ❑Fail ❑Pass ❑Fail <br /> Was sensor removed for testing? ✓❑Yes ❑No ❑NA ✓❑Yes [-]No ❑NA ❑Yes❑No ❑NA ❑Yes ❑No ❑NA <br /> Was sensor properly replaced and ✓Yes No NA ❑✓Yes No NA ❑Yes No NA ❑Yes No <br /> verified functional after testing? ® ❑ ® ® ❑ ❑ ❑ ❑ ❑NA <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> p <br /> MAR 3 0 ZOW <br /> "tdr <br /> Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23,Section 2637(a)(6)} <br />
The URL can be used to link to this page
Your browser does not support the video tag.