Laserfiche WebLink
Alk <br /> CONTINUATION FORM Page: 2 <br /> OFFICIALDate: 05/10/07 <br /> FacilityAddress: 4 W Hammer Ln P ram: UST <br /> UST Monitoring Certification Inspection Report <br /> 021 Liquid was observed In the 1/2 dispenser pan. All secondary containment must be kept <br /> free of liquid at all times to adequately determine the presence of a leak. Immediately <br /> remove this liquid and handle per Title 22 Hazardous Waste regulations. Service <br /> technician removed this liquid at the time of Inspection. <br /> 025 The diesel leak detector cold not bet tested at the time of inspection. This leak detector <br /> was last tested on March 27,2006 and Is two months late. All leak detectors must , <br /> tested once every 12 months. Immediately schedule this test within the next 7 days. <br /> Notify this office at least 48 hours prior to testing. Note: The service technician believes <br /> there is not enough fuel in the tank to prime the line. Additional fuel may be needed to <br /> dorm this test <br /> Note: Testing of the 91 and diesel spill buckets were not witnessed by this office. Should either <br /> of these fall, Immediately obtain a grmit toreit or replace from this office. <br /> THIS FACILITY 15 SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY <br /> � �AEJ , ltp�A� -jo Q�ArJ 5AK&kL51d <br /> SAN JOAQUIN COUNTY ENVIRONMENTAL HEALTH DEPARTMENT-304 E WEBER AVE,STOCKTON,CA 96202 (209) 20 <br /> MW 23-02-0}3 <br />