Laserfiche WebLink
CONTINUATION FORM Page: 2 <br /> FICIAL INSPECTION REPORT Date: 05/10/07 <br /> Facility Address: 3304 W Hammer Ln Program: UST <br /> UST Monitoring Certification Inspection Report <br /> 21 Liquid was observed in the 1/2 dispenser pan. All secondary containment must be kept <br /> free of liquid at all times to adequately determine the presence of a leak. Immediately <br /> remove this liquid and handle per Title 22 Hazardous Waste regulations. Service <br /> technician removed this liquid at the time of inspection. <br /> 25 The diesel leak detector cold not bet tested at the time of inspection. This leak detector <br /> was last tested on March 27, 2006 and is two months late. All leak detectors must be <br /> tested once every 12 months. Immediately schedule this test within the next 7 days. <br /> Notify this office at least 48 hours prior to testing. Note: The service technician believes <br /> there is not enough fuel in the tank to prime the line. Additional fuel may be needed to <br /> perform this test. <br /> Note: Testing of the 91 and diesel spill buckets were not witnessed by this office. Should either <br /> of these fail, immediately obtain a permit to repair or replace from this office. <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> EHD Inspector: Received By: Title: <br /> SAN JOAQUIN COUNTY ENVIRONMENTAL HEALTH DEPARTMENT-304 E WEBER AVE,STOCKTON,CA 95202 (209)468-3420 <br /> EHD 23-02-003 <br />