Laserfiche WebLink
Client: Stericycle Inc <br />Project/Site: SMF3 <br />Job ID: 400-191724-1 <br />Laboratory: Eurofins TestAmerica, Pensacola <br />Narrative <br />Case Narrative <br />Job Narrative <br />400-191724-1 <br />Job ID: 400-191724-1 <br />Comments <br />No additional comments. <br />Receipt <br />The sample was received on 8/5/2020 9:55 AM. The temperature of the cooler at receipt was 27.7° C. <br />Receipt Exceptions <br />The Chain -of -Custody (COC) was incomplete as received. Client did not fill out sample time, sample date, or analysis. Defulated to use <br />the day previous for sample date and 00:00 for sample time. <br />Metals <br />Method 60106: The following sample was diluted due to the presence of iron which interferes with lead, antimony and thallium.SAMPLE <br />1 SMF3 (400-191724-1). Elevated reporting limits (RLs) are provided. <br />Method 60106: The laboratory control sample (LCS) and / or laboratory control sample duplicate (LCSD) for preparation batch 400-499450 <br />and 400-499605 and analytical batch 400-499976 recovered outside control limits for the following analytes: Molybdenum. These analytes <br />were biased high in the LCS and were not detected in the associated samples; therefore, the data have been reported. <br />No additional analytical or quality issues were noted, other than those described above or in the Definitions/Glossary page. <br />General Chemistry <br />No analytical or quality issues were noted, other than those described in the Definitions/Glossary page. <br />Organic Prep <br />No analytical or quality issues were noted, other than those described in the Definitions/Glossary page. <br />Eurofins TestAmerica, Pensacola <br />Page 3 of 23 <br />