Laserfiche WebLink
110 2nd Avenue South,iMD7,Pacheco,GA 9 5553-5560 <br /> MCCampbell Analytical Inc. Telephone:925-798-1620 Fax:925-798-1622 <br />' http://www.meeampbell.eom E-mail:inain@Tcemnpbcll.com <br /> QC SUMMARY REPORT FOR SW8015C <br /> Matrix:W WorkOrder: 0211025 <br />' -EPA Method: SW8015C Extraction: SW3510C BatchiD:4719 Spiked Sample ID: N/A <br /> Sample I Spiked MS* MSD* IMS-MSWLCS LCSD I LCS-LCSD Acceptance Criteria(%) <br /> Compound — — <br />' wg/L pg/L %Ree. %Rec. ! %RPD i % Rec. %Rec. % RPE) I Low High <br /> TPH(d) NIA 7500 N/A N/A N/A 96.9 92.6 4.5470 130 <br /> %SS: - NIA 100 N/A- N/A N/A 116 I 110 _ 5.63 70 130 <br /> Ii <br /> All target compounds in the Method Blank of this extraction batch were ND less than the method RL with the following exceptions: <br />' NONE <br /> I <br />' M5=Matrix Spike;MSD=Matrix Spike Duplicate;LCS=Laboratory Control Sample;i CSD=Laboratory Control Sample Duplicate;RPD=Relative Percent <br /> Deviation. <br /> . NIA=not enough sample to perform matrix spike and matrix spike duplicate. <br /> NR=analyte concentration in sample exceeds spike amount for sail matrix or exceeds 2x spike amount for water matrix of sample diluted due to high matrix or <br />' analyte content. <br /> %Recovery=too*(MS-Sample)!(Amount Spiked);RPD=100*(MS—MSD)I(MS+MSD)*2. <br /> *MS and/or MSD spike recoveries may not be near 100%or the RPDs near 0%if:a)the sample is inhomogenous AND contains significant concentrations of <br />' analyte relative to'the amount spiked,or b)if that specific sample matrix interferes with spike recovery. <br />