A J OA U I Environmental Health Department <br /> COUNTY <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> AHMEDS SONS INC 1 1257 W YOSEMITE AVE, MANTECA April 20, 2020 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 209 CCR 2716(a-e) Failure to conduct the designated UST operator visual inspection at least once every 30 days. <br /> OBSERVATION: The designated operator failed to check and note all required items on the visual inspection <br /> reports. The incorrect and missing information included the following from the inspection reports: <br /> -The 04/01/2020 DO report did not include the owner/operator name and date signed <br /> -The 10/15/2019, 8/20/2019, 7/22/2019, 6/20/2019, and 4/23/2019 DO reports did not include the owner/operator <br /> name <br /> -The 4/23/2019, 6/20/2019, 7/22/2019, 8/20/2019, 9/17/2019, 10/15/2019,11/13/2019, 12/11/2019, 1/8/2020, <br /> 2/5/2020,3/4/2020, and 4/1/2020 <br /> DO reports failed to mark Yes or No to the question "Have all individuals performing facility employee duties <br /> received the required facility employee training within the past 12 months?" (Section XI), and the <br /> The DO reports failed to write the zip code. <br /> The DO reports incorrectly stated that the overfill prevention was conducted on 04/10/2019 the current date was <br /> 3/10/2019. <br /> -The 06/20/2019 DO report was performed more than 30days after the previous inspection. Initial inspection <br /> performed on 4/22/2019, next inspection performed on 6/20/2019, 61 days between the two dates. <br /> REGULATION GUIDANCE: During the visual inspection, the designated operator shall check that all required <br /> testing and maintenance for the UST system have been completed and shall check all required items on the report. <br /> CORRECTIVE ACTION: Ensure that designated operators performing visual inspections at this facility are including <br /> all of the required information on the reports. <br /> This is a minor violation. <br /> 313 HSC 25290.1, 25290.2, 25291 Failure to construct, operate, and maintain primary containment as product-tight. <br /> OBSERVATION: Seepage was detected below the shear valve in under dispenser containment (UDC)# 1/2, 5/6 and <br /> 7/8 indicating a leak in the primary containment. <br /> REGULATION GUIDANCE: All primary containment for the UST system must be product tight. <br /> CORRECTIVE ACTION: Immediately have a properly licensed, trained, and certified contractor repair or replace the <br /> failed component(s), under permit and inspection of the EHD if necessary. <br /> This is a minor violation. <br /> FA0003707 PR0231463 SCO01 04/20/2020 <br /> EHD 23-01 Rev.9/20/2019 Page 5 of 7 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />