+ 'i jili li \ Ii t , it 111 <br /> S 0 I ` ; W1 i; l3 Environmental Health Department <br /> J 1, .. � 'J�i �alltG � t _ i �' ; <br /> [- IZ I tN i g_ j <br /> . .._ _... CUUN I Y T <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> WESTERN FOOD & FUEL 3032 E WATERLOO RD , STOCKTON December 11 , 2018 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS 11 CLASS II, or MINOR - Notice to Comply) <br /> Item # Remarks <br /> 306 CCR 2630 (d) Monitoring equipment is not installed or maintained to detect a leak at the earliest opportunity. <br /> The site has flexible primary and secondary piping . During the field inspection it was observed that the test boots <br /> appeared completely sealed in the 87 product and 91 product lines in all UDCs. Any potential release from the <br /> primary containment into the secondary containment in the 87 product and 91 product piping does not flow into a ! <br /> UDC collection sump to detect a leak at the earliest opportunity. Immediately contact a properly licensed , trained , <br /> and certified contractor to ensure that any releases in the 87 product and 91 product piping flows into the nearest <br /> sump for a leak to be detected at the earliest possible opportunity. Ensure that all monitoring equipment is <br /> maintained to detect a leak at the earliest opportunity. <br /> i <br /> i <br /> This is a Class I violation . <br /> 307 CCR 2631 (g) , 2632(c) Monitoring system of the interstitial space of a double walled system not maintained . <br /> The 91 product and diesel product split tank annular sensor failed to come out of audible and visual alarm when <br /> tested and , therefore, the tank is not monitored . The interstitial space shall be monitored with a monitoring system <br /> connected to an audible and visual alarm system. The sensor was replaced and retested during the inspection. A <br /> " UST Retrofit Verification with Inspector Already Onsite" form has been completed and provided to the operator and <br /> contractor. <br /> This is a repeat violation , Class IL <br /> i <br /> 318 CCR 2636 (0(2) Leak detector failed to detect a 3.0 gallons per hour leak at 10 pounds per square inch . E <br /> The 87 product VMI line leak detector failed to detect a leak when tested . All line leak detectors shall be capable of <br /> detecting a 31allon per hour leak at 10 psi. The service technician adjusted the leak detector, retested it, and it <br /> passed. <br /> This is a repeat violation , Class Il , <br /> 320 CCR 2635 , 2637. 21 2665 , 2712 Failure to comply with the installation , inspection , or record keeping of the overfill <br /> prevention. <br /> Owners or operators of underground storage tanks that do not meet Califomia Code of regulations, title 23 division <br /> 3, chapter 16 section 2635(c)(2) shall test overfill prevention equipment once by October 13th , 2018 and every 36 <br /> months thereafter; and within 30 days of the date of a repair. The site did not performed the testing by October 13th , <br /> 2018 however the service technician on site was able to conduct the overfill prevention equipment inspection today <br /> ( 12/11 /18) while the inspector was on site. Ensure to conduct overfill prevention equipment inspection within the <br /> time frame provided by the regulation and submit test results within 30 days of performing the inspection . Ensure a <br /> 48 hour notification is provided to EHD prior to conducting the inspection. <br /> This is a Class II violation. <br /> Overall Inspection Comments . <br /> An inspection checklist was provided to the facility operator on the day of inspection . The EHD has written the <br /> complete report which replaces the initial checklist. <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> FA0002127 PR0231758 SCO01 12/11 /2018 <br /> EHD 2301 Rev. 09128/2018 Page 7 of 8 Underground Storage Tank Program OIR <br /> 1868 E . Hazelton Avenue I Stockton , California 95205 1 T 209 468-3420 I F 209 464-0138 1 www. sjcehd . com <br />