Laserfiche WebLink
VISUAL INSPECTION OF INTERIOR: Good Condition <br /> TANK PARAMETERS ON INSPECTION: No leakage Between Walls <br /> SECONDARY CONTAINMENT. Good Condition <br /> CONTAINMENT VOLUME Estimated at 125%of tank volume <br /> CONTAINMENT CONDITIONS: Good Condition <br /> CONTAINMENT AMOUNT Estimated at 125% of tank volume <br /> GENERAL TANK CONDITIONS Good Condition <br /> TANK INTEGRITY TEST: Pressure test for one hour at 5 Psi min <br /> TEST PROCEDURE Plug all openings pressure to 5.0 PSI (Actual Pessure this test at 6 Psi.) <br /> LEAKS: Check for leaks and tank failure <br /> None Found <br /> EQUIPMENT USED FOR TEST: Air Pressure Gauge <br /> With Pipe Plugs <br /> TIME Pressure <br /> 09:05 AM 6.0 Psi. <br /> 09:15 AM 6.0 Psi. <br /> 09:30 AM 6.0 Psi <br /> 10:05 AM 6.0 Psi <br /> RETURN TANK TO SERVICE: 1:PM Antifreeze Tank Passed Pressure Test <br /> PRESSURE ON BOTTOM OF TANK 6.6 PSI with 2'of Antifreeze <br /> TANK FILL PIPING AND FEED PUMP Husky 1040 Feeds Tank Through Hose and Steel Pipe <br /> OPERATION OF TANK AND EQUIP: M-F. 8 AM to 5 PM <br /> SECURITY DURING OPEN HOURS Open to the Public Traffic under employee subervision <br /> SECURITY DURING CLOSED HOURS Chain link fence with locked gates <br /> MATERIAL STORED: Used Antifreeze Ethylene Glycol 50 to 80 precent by volume <br /> Used Diethylene Glycol 0 to 5 percent of volume <br /> SPECIFIC GRAVITY: +1.0 and veries <br /> (Characteristic of used antifreeze not modified 6118120) <br /> CHEMICAL CAPABILITY Non-corrosive to Steel <br /> RECOMMENDATION 1. Daily Inspection with Record Sheet should be attached to this tank <br /> I certify under penalty of law that this document and all attachments were prepared under my <br /> direction or supervision in accordance with a system designed to assure that qualified personnel <br /> properly gather and evaluate the information submitted. Based on my inquiry of the person or <br /> persons who manage the system, or those persons directly responsible for gathering the <br /> information,the information submitted is,to be the best of my knowledge and belief, true, <br /> accurate, and complete. I am aware that there are significant penalties for submitting false <br /> information, including the possibility of fine and imprisonment for knowing violations. <br /> THIS REPORT PREPARED BY ERVIN RIFENBURG RCE 19752 O pp,OFESSIppjq� <br /> OF FOOTHILL ENGINEERING �zc� �14?kIFPN� <`y� <br /> 2091368-9381 Sign G m+ <br /> 12793 Paddy Creek Lane, , <br /> Lodi, Ca. <br /> PAGE 2 F OF Glk� <br />