Laserfiche WebLink
Environmental Health DepartmentUnderground Storage Tank Program Inspection ReportDate:May 18, 2020Facility Address:8115 S EL DORADO ST, FRENCH CAMPFacility Name:J & L MARKETSUMMARY OF VIOLATIONS(CLASS I, CLASS II, or MINOR - Notice to Comply)RemarksItem #211CCR 2715(c)(2) No employee present that were trained in the operation and maintenance of the UST system by a DO. OBSERVATION: The designated operator employee training for Erika Romero was not current. REGULATION GUIDANCE: The designated operator shall train facility employees in the proper operation and maintenance of the UST system at least once every 12 months. The training shall be conducted before the individual performs the duties of a facility employees. The training shall include, but is not limited to: 1. Operation of the UST system in a manner consistent with the facility’s best management practices 2. Employee’s role with regard to monitoring equipment as specified in the facility’s monitoring plan 3. Employee’s role with regard to spills and overfills as specified in the facility’s response plan 4. Name of the contact person(s) for emergencies and monitoring equipment alarmsInitial training shall also include a site-specific practical demonstration that provides both sharing information and evaluating knowledge for responding to emergencies, leak detection, monitoring alarms, spills and overfills. At least one of the facility employees present during operating hours shall have current training. CORRECTIVE ACTION: Ensure that employees have been trained by the designated operator, maintain the list on site, and submit a copy of the training records to the EHD.This is a minor violation.Overall Inspection Comments:The monitoring system certification was conducted on 5/18/2020 and the paperwork inspection completed today (5/19/2020). An inspection checklist was provided to the facility operator on the day of inspection. The EHD has written the complete report which replaces the initial checklist.Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement documenting the corrective actions that have been or will be taken for each violation, and any supporting paperwork, by 06/18/2020.To minimize person to person contact EHD is choosing to write the name of person receiving the report instead of having them sign. Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate ($152). To schedule an appointment, please call (209) 468-3420.Documents provided: Return to compliance certificatio form and corrective action form.AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING THIS FACILITY BACK INTO COMPLIANCE.THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. Received by: Inspector Phone:(209) 468-3432 PAUL NSO, EHS Trainee Inspector:May 19, 2020 Date:Printed Name and Title:Erika Romero, CashierFA0000110 PR0231563 SC001 05/18/2020EHD 23-01 Rev. 9/20/2019Underground Storage Tank Program OIRPage 6 of 61868 E. Hazelton Avenue | Stockton, California 95205 | T 209 468-3420 | F 209 464-0138 | www.sjcehd.com