Laserfiche WebLink
3. PIPING SUMP TESTING <br /> Company Name: B.Z. Service Station Maintenance <br /> Company Address: 1041 Triangle Ct.,West Sacramento,CA 95605 <br /> Credentials: ®CSLB Licensed Contractor Q SWRCB Licensed Tank Tester <br /> t,icense Type: ICC License Number:433159 <br /> TURBINE/PRODUCT PIPING SUMPS ® VENT/TRANSITION SUMPS ❑ <br /> *Fquif,,ment Used: INCON TS-STS Equipment Resolution:0.0001 <br /> Sump#87 Sump# DSL Sump# Sump# <br /> mp Tested' 25" 16" <br /> Does turbine shut down when <br /> sump sensor detects liquid(both ® Yes❑No❑NA ®Yes❑No❑NA ❑ Yes❑No❑NA C]Yes❑No❑NA <br /> product and water)?* <br /> Turbine shutdown response time 5sec 5sec <br /> Is system programmed for fail-safe <br /> shutdown?' ®Yes❑No❑NA ®Yes❑No❑NA ❑Yes❑No❑NA F-1 Yes❑No Q NA <br /> Was fail-safe verified to be ®Yes❑No Q NA ®Yes Q No❑NA ❑Yes❑No❑NA Q Yes❑No❑ NA <br /> o erational?* <br /> Wait time between applying <br /> pressure/vacuum/water and starting 15min 15min <br /> test: <br /> Test Start Time: 11:31 11:56 <br /> Initial Reading(Ri): 1.6810 2.0992 <br /> Test End Time: 11:46 12:11 <br /> Final Reading(RF): 1.6798 2.0990 <br /> Test Duration: 15 MIN 15 MIN 15 MIN 15 MIN <br /> Change in Reading(RF-Ri): 0.0012 0.0002 <br /> Pass/Fail Threshold or Criteria: 0.002 0.002 0.002 0.002 <br /> Test Result: ® Pass Q Fail ®Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Was sensor removed for testing? ®Yes❑No❑NA ®Yes❑No❑NA Q Yes❑No Q NA ❑Yes❑No❑NA <br /> Was sensor properly replaced and ® Yes Q No❑NA ®Yes El No El NA ❑Yes El No F-1NA ❑Yes❑No❑NA <br /> verified functional after testin�? <br />