Laserfiche WebLink
Spill Bucket Testing Report <br /> 1. FACILITY INFORMATION <br /> Facility Name: ARP Mini Mart Mobil Date of Testing: 02/20/2020 <br /> Facility Address: 25775 S.Patterson Rd. Tracy,CA 95376 <br /> Facility Contact: Neil Patel Phone: (510)299-1219 <br /> 2. TESTING CONTRACTOR INFORMATION <br /> Company Name: Diamond Petroleum Services,Inc. <br /> Technician Conducting Test: Guadalupe Sanchez <br /> Contractor License# 1005444 ICC Certification#5250451 <br /> 3. SPILL BUCKET TESTING INFORMATION <br /> Test Method Used: Hydrostatic <br /> Test Equipment Used: Standard Tape Measure Equipment Resolution: 1/16" <br /> Identify Spill Bucket(By Tank Tl:87 Slave Fill T2:87 Master Fill T3: Diesel Fill T4: 91 Fill <br /> Number,Stored Product, etc. <br /> Bucket Installation Type: Direct Bury Direct Bury Direct Bury Direct Bury <br /> x Contained in Sump x Contained in Sump x Contained in Sump x Contained in Sum <br /> Bucket Inside Diameter: 11 '/," 11 '/." 11 %." 11 'h" <br /> Bucket Depth: 17" 16" 17" 16" <br /> Wait time between,applying 5 minutes 5 minutes 5 minutes 5 minutes <br /> vacuurn4ater and start of test: <br /> Test Start Time(TI): 10:10 a.m. 10:10 a.m. 10:11 a.m. 10:10 a.m. <br /> Initial Reading(Ri): 14 3/8" 14 ''/2" 14 %2" 141/2" <br /> TegtEnd Time(TF): 11:10 a.m. 11:10 a.m. 11:11 a.m. 11:10 a.m. <br /> Final Reading(RF): 14 3/8" 14 %2" 14 V2" 141/2" <br /> Test Duration(TF—T,): 1 hr 1 hr 1 hr 1 hr <br /> Change in Reading(RF-Ri): 0 0 0 0 <br /> Pass/Fail Threshold or 1/8" 1/8" 1/8" 1/8" <br /> Criteria: <br /> Test Result: x Pass Fail x Pass Fail x Pass Fail x Pass Fail <br /> Comments: <br /> Technician's Signa e• Date: 02/20/2020 <br />