Recommended Practices for the Testing and Verification of Spill,overfill, Leak Detection and Secondary Containment Equipment at UST Facilitie! <br /> NOTE: If the fill cap. is not included in the the spill bucket.The vacuum level is monitored fol <br /> spill bucket test and/or the cap is not tight, it a 1-minute period. <br /> could be the source of potential fuel contami- 6.3.3 Test Equipment. Test equipment shal <br /> nation from water intrusion. <br /> - include: <br /> NOTE: Before permanently plugging, ensure ° vacuum test apparatus (The test apparatus may <br /> that local regulations allow the drain valve to be available from the spill bucket manufacturer <br /> be permanently plugged. It includes an air pressure regulator, a vacuurr <br /> - - . . . source, a vacuum gauge with a minimum 0-5( <br /> inch water column range and a control valve <br /> 6.2.5 Test Procedure. The control valve is used to adjust the vacuurr <br /> 1. Add water to the spill bucket to a level within level.); <br /> 1.5 inches of the top of the spill bucket. Allow o test cover(The cover is equipped with a test fit• <br /> the water to settle for 5 minutes before the initial ting.); <br /> water level measurement is taken. <br /> 2. Place the measuring stick vertically at the lowest plumber's plug (appropriate size, if used); <br /> point in the spill bucket and extending above the ° stopwatch or other time-measurement device <br /> water level to allow for an accurate measure- capable of measuring a 1-second increment; <br /> ment to be taken. The location of the measuring o gasketing material (The purpose of the gas- <br /> stick must remain the same for each water level keting material is to provide an air-tight sea: <br /> measurement. Document the initial water level between the test cover and the spill bucket.). <br /> measurement as measured from the bottom of <br /> the spill bucket.Alternative measurement meth- o-50-water column <br /> ods may be used provided that measurement to Vacuum Vacuum Gauge <br /> 1/16(0.06:3) inch can be made, source <br /> 3.Take all precautions to prevent the water level <br /> from being; disturbed during the duration of the control <br /> test. Valve <br /> 4. After 1 hour, document the ending water level <br /> measurement. <br /> 5. Upon completion of the test, remove and dis- <br /> pose of the water according to Section 6.7, and <br /> dry the inside of the spill bucket before returning , Plumber's Plug In <br /> it to service. Tank Riser Pipe <br /> 6.2.6 Pass/Fall Criteria. If the water level has <br /> dropped less than 1/8 (0.125) inch,the spill bucket <br /> passes the integrity test. <br /> If the water level has dropped 1/8 (0.125) inch or <br /> greater, the spill bucket fails the integrity test. <br /> 6.3 Spill Bucket Integrity Testing — Vacuum Test FIGURE,6-2. The cover must make a tight seal with the <br /> Method. spill bucket to prevent leakage when the vacuum is <br /> 6.3.1 Purpose. This method is used to test the pulled during the test. <br /> integrity of single-walled spill buckets or the pri- <br /> mary containment of secondarily contained spill _ <br /> buckets. 1, t\i„ZI,IiIS�iCi� Use only an air-operated vac- <br /> uum source or a vacuum pump pow- <br /> 6.3.2 Description of Test. Using a specially, ,, ered by an explosion-proof motor. Vacuum <br /> equipped test cover, a partial vacuum is app'U' d`t6'`' pumps with electric motors that are not <br /> ENVIRONMENTAL HEAL) H Im <br /> DEPARTMENT pei.org fff E1IWE <br />