Laserfiche WebLink
TA I T <br /> 2!3! S.^up::.,.D-,N2, nr�n",�, ,rq 4205 <br /> p:714156018222 www.ta it.com <br /> Test Date: 11/09/2018 <br /> LEAK DETECTOR TESTING <br /> Facility ID: 01 Client Name: Unified Grocers, Inc <br /> Street Address: 1990 Piccoli Rd. Technician: Pat Banbury <br /> City: Stockton ICC#: 5254955 <br /> Zip Code/State: 95215 ! CA Manufacturer Cert#: 1786/1001733709 <br /> Test Information <br /> Product Diesel Diesel <br /> Manufacturer Vaporless Fe Petro <br /> Model LD-3000 STP-MLD-D <br /> New Leak Detector No No <br /> Yes/No <br /> Serial Number 00310065 MH-1393 <br /> Electronic LD No No <br /> Yes/No <br /> Calibrated Test Leak <br /> Rate: (189 mil/min Yes Yes <br /> 10 PSI) Yes/No <br /> Check Valve Holding 40 13 <br /> PSI <br /> Resiliency 350 150 <br /> (Bleed Back MIL) <br /> Slow Flow 25 11 <br /> Metering PSI / N/A <br /> Turbine Shut Down <br /> Electronic LD N/A N/A <br /> Yes/No/NA <br /> Slow Flow At Nozzle Yes Yes <br /> Yes/No/NA) <br /> Opening Time 4 6 <br /> (Seconds) <br /> Pass/Fail Pass Pass <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility <br /> according to the equipment manufacturers procedures and limitations and the results as listed are to my <br /> knowledge true and correct. The leak detector test pass/fail is determined using a low flow threshold trip <br /> rate of 3 gph at 10 PSI. <br /> Technician Signature: Date: 11/09/2018 <br /> CA Ilc#588098 1 AZ lick 0959941 NV lick 0049666 t TX lick CR0000041 <br /> 3.21.16.1 <br />