Laserfiche WebLink
Ili TAIT <br />u 1 Ei Wilinrbt 21,31 S. DArpt.r... tthls..‘411 , CA 1291.1f.: <br />406018222 wwwIoIIcom <br />Test Date: 11/09/2018 <br />LEAK DETECTOR TESTING <br /> <br />Facility ID: 01 <br /> <br />Client Name <br />Technician. <br />ICC #: <br />Manufacturer Cert <br /> <br />Unified Grocers. Inc <br /> <br />Street Address: 1990 Piccoli Rd. <br /> <br />Pat Banbury <br />City: Stockton <br /> <br />5254955 <br />Zip Code / State: 95215 <br /> <br />/ CA <br /> <br />1786/ 1001733709 <br /> <br />Test Information <br />Product Diesel Diesel <br />Manufacturer Vaporless Fe Petro <br />Model LD-3000 STP-MLD-D <br />New Leak Detector <br />(Yes/No) No No <br />Serial Number 00310065 MH-1393 <br />Electronic LD <br />(Yes/No) No No <br />Calibrated Test Leak <br />Rate: (189 mil/min <br />@ 10 PSI) (Yes/No) <br />Yes Yes <br />Check Valve Holding <br />PSI 40 13 <br />Resiliency <br />(Bleed Back MIL) 350 150 <br />Slow Flow <br />Metering PSI / (N/A) 25 11 <br />Turbine Shut Down <br />Electronic LD <br />(Yes/No/NA) <br />N/A N/A <br />Slow Flow At Nozzle <br />(Yes/No/NA) Yes Yes <br />Opening Time <br />(Seconds) 4 6 <br />Pass/Fail Pass Pass <br />This letter certifies that the annual leak detector tests were performed at the above referenced facility <br />according to the equipment manufacturers procedures and limitations and the results as listed are to my <br />knowledge true and correct. The leak detector test pass/fail is determined using a low flow threshold trip <br />rate of 3 gph at 10 PSI. <br />Technician Signature: pat Eaitictize, <br /> <br />Date: 11/09/2018 <br /> <br />CA Hot 538098 I AZ licit 095984 / 110 0049666 / TX lid/ CR0000041 <br />321 16.,