Laserfiche WebLink
The following is an itemized list of underground storage tank violations that have not <br />been addressed for DINO MART as of Apri128, 2020. <br />Open violations from January 13, 2020 inspection <br />Violation #320 - Failure to comply with the installation, inspection, or record keeping of the overfill <br />prevention. <br />OBSERVATION The diesel mechanical flappers used as the overfill prevention system were marked as failures on <br />the 10/11/18 Overfill Prevention Equipment Inspection Report. <br />REGULATION GUIDANCE: All UST systems must be equipped with an approved, functional overfill prevention <br />device at all times during delivery operations. <br />CORRECTIVE ACTION: Immediately discontinue deposition of petroleum into this tank until the component is <br />repaired or replaced by a properly licensed, trained, and certified contractor under permit and inspection of the EHD. <br />If the failed component can't be replaced immediately, there is a possibility that the diesel UST system may be red <br />tagged to prevent fuel inputs. <br />❑ This violation was corrected ❑ This violation will be corrected by (date): <br />❑ Supporting documents included <br />Describe actions taken or will be taken to correct violation: <br />Page 1 of 1 <br />