Laserfiche WebLink
LABORATO)2Y CONTROL SAMPLE EVALUATION REPORT <br /> GC/NIS Volatiles <br /> Client Lot ##. . . : GOH260141 Work Order ##. . . : DKFE0102-L,CS Matra_x- - - - - - - - - -- WATER <br /> LCS Lot--Sample#-- GOIISOOOO-310 DKF'E0103-1,CSD <br /> Prep Date. . . . . . .. 09/08/00 Analysis Date_ . -- 09/08/00 <br /> Prep Batch #). . . -- 0259310 <br /> Dilution Factor: I <br /> OERCENT RECOVERY RPD <br /> PARAMETER RECOVERY LIMITS RPL LIMITS METHOD <br /> Benzene 104 (70 - 130) - SW846 8260B <br /> 111 (70 - 130) 6.0 (0-35) SW046 8260B <br /> Ch:lorobenzene 102 (70 - 130) SW846 8260B <br /> 107 (70 - 130) 5.5 (0-35) SW846 8260B <br /> 1,1--Dzchloroethene 11.3 (70 - 130) SW846 8260B <br /> L21 (70 - 130) 6.9 (0-35) SW846 8260B <br /> Toluene 103 (70 - 130) SW846 8260B <br /> 109 (70 130) 5.7 (0-35) SW846 8260B <br /> Trichloroethene 101 (70 - 1.30) SW846 8260E <br /> - <br /> 110 (70 130) 8.8 (0-35) SW846 8260B <br /> PERCENT RECOVERY <br /> SURROGATE RECOVERY L114ITS <br /> 4-Bromofluorobenaene 91 (7C - 130) <br /> 93 (70 - 130) <br /> 1,2-Di-chloroethane-d4 72 (70 130) <br /> 78 (70 - 130) <br /> Toluene-de 94 (70 - 130) <br /> 97 (70 - 130) <br /> NOTE(S) <br /> Calculsuom are performed before mtmdmg to avoid mund-off errors m calculated results <br /> Bold prim demmes control parameters <br /> i <br />