uWIN=r, <br /> i <br /> April 12, 198 <br /> TEST DATA & RESULTS <br /> Page 1 <br /> A\-- <br /> Mary Ann Mans er <br /> SUNNYSIDE PRODUCE I� <br /> P. 0. Box 433 Site: 8960 W. Walnut Grove Road <br /> Thornton, California 95686 Thornton, California . <br /> Dear Ms . Manser: <br /> The following is a summary of the precision testing we recently <br /> conducted on your underground storagetank (s) . I <br /> Enclosed are copies of the test worksheets and graphs generated <br /> during'-the testing. They are provided for <br /> appropriate govenmental agency. Your submittal to the <br /> A tank system is considered tight, according to the current <br /> regulations, if the gain. is less than .02 or the loss is less than .05 <br /> gallons per. one hour of testing. If the results shown below are <br /> beyond these parameters, you will need to take 'remedial action. <br /> Please note page 2 of this letter if a no is shown <br /> below, in the final colurtn <br /> TANK # TANK PRODUCT TEST WITHIN "TIGHT" <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> South 10, 300 U/L Gas -.16527 No <br /> i <br /> ie <br /> Please contact us if you need additional assistance or <br /> information. II <br /> Sincerely, .� <br /> a <br /> W. S vage <br /> Certified Tester <br /> I <br /> 00;=2� "�83�8 1'fi`��FYa ��IV�es#Circle � ;Stockt n; �:A�4� 0 ZQ9)d6�6-s$Q �u <br /> II <br />