Laserfiche WebLink
SAN J O A R N Environmental Health Department <br /> -:a U ;� i _# �V AMENDED <br /> 6/19/2020 <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> RYDER TRUCK RENTAL#1071 3633 DUCK CREEK DR, STOCKTON January 09, 2020 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> CORRECTIVE ACTION: Ensure that designated operators performing inspections at this facility are including all of <br /> the required information on the reports. <br /> 5)OBSERVATION:The designated operator failed to check and note all required items on the visual inspection <br /> reports.The incorrect and missing information included the following from the inspection reports: <br /> -Several items were marked as"NA"on the inspection report and were not documented in Section III. <br /> -Sections VII and VIII were left blank. <br /> -Tank and line tightness test information was left blank. <br /> -The designated operator documented visual inspections of sumps, but left the question regarding sump sensor <br /> locations blank. <br /> -The designated operator documented visual inspections of UDCs, but left the question regarding UDC sensor <br /> locations blank. <br /> REGULATION GUIDANCE: During the visual inspection,the designated operator shall check that all required <br /> testing and maintenance for the UST system have been completed and shall check all required items on the report. <br /> CORRECTIVE ACTION: Ensure that designated operators performing visual inspections at this facility are including <br /> all of the required information on the reports. <br /> This is a repeat violation, Class ll. <br /> 211 CCR 2715(c)(2) No employee present that were trained in the operation and maintenance of the UST system by a <br /> DO. <br /> OBSERVATION: The designated operator employee training for employees was not performed. <br /> REGULATION GUIDANCE: The designated operator shall train facility employees in the proper operation and <br /> maintenance of the UST system at least once every 12 months. The training shall be conducted before the <br /> individual performs the duties of a facility employees.The training shall include, but is not limited to: <br /> 1. Operation of the UST system in a manner consistent with the facility's best management practices <br /> 2. Employee's role with regard to monitoring equipment as specified in the facility's monitoring plan <br /> 3. Employee's role with regard to spills and overfills as specified in the facility's response plan <br /> 4. Name of the contact person(s)for emergencies and monitoring equipment alarms <br /> Initial training shall also include a site-specific practical demonstration that provides both sharing information and <br /> evaluating knowledge for responding to emergencies, leak detection, monitoring alarms, spills and overfills. At least <br /> one of the facility employees present during operating hours shall have current training. <br /> CORRECTIVE ACTION: Ensure that employees have been trained by the designated operator, maintain the list on <br /> site, and submit a copy of the training records to the EHD. <br /> This is a repeat violation, Class ll. <br /> Overall Inspection Comments: <br /> The monitoring system certification was conducted on 1/9/2020. The testing was not witnessed in its entirety. <br /> FA0003758 PR0232461 SCO01 01/09/2020 <br /> EHD 23-01 Rev.9/20/2019 Page 7 of 8 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />