Laserfiche WebLink
SAN J O A R N Environmental Health Department <br /> i , �V <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> GRANT LINE SHELL* 2375 W GRANT LINE RD,TRACY May 18, 2020 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 124 CCR 2637.2(d&e), 2665(a&b)"Overfill Prevention Equipment Inspection Report Form" not submitted within 30 days <br /> of inspection. <br /> OBSERVATION: The Overfill Prevention Equipment Inspection was performed on 5/2/2019 and a test report was <br /> submitted on 5/12/2020, 12 months late. <br /> REGULATION GUIDANCE:A copy of the test report must be submitted within 30 days of the tests. <br /> CORRECTIVE ACTION: Take all necessary precautions to ensure testing and submittal of test reports are <br /> performed in a timely manner. <br /> This is a repeat violation, Class II. <br /> 201 CCR 2712(b)(1-2)Failure to maintain monitoring, maintenance, and follow up action records. <br /> OBSERVATION: Secondary containment test result for 4/7/2020 were not found on site. <br /> REGULATION GUIDANCE: These records shall be maintained on site for at least three years. Monitoring records <br /> include: (1)date and time of all monitoring or sampling; (2)monitoring equipment calibration and maintenance <br /> records; (3)results of any visual observations; (4)results of sample analysis performed a lab or in the field; (5)logs <br /> of all readings of gauges or other monitoring equipment, ground water elevations, or other test results; (6)results of <br /> inventory readings and reconciliations. <br /> CORRECTIVE ACTION: Immediately locate and maintain all missing maintenance and monitoring records for the <br /> last three years on site and submit copies to the EHD. <br /> This is a repeat violation, Class Il. <br /> 202 CCR 2715(c)(3), 2715(c)(4) Failure to maintain the"Facility Employee Training Certificate"on-site(after October 1, <br /> 2018). <br /> OBSERVATION: The Facility Employee Training Certificate attached to the 6/6/2019 monthly inspection report was <br /> missing the signature of the designated operator and training date. <br /> REGULATION GUIDANCE:All site employees must be trained prior to taking responsibility as a facility employee if <br /> after October 1, 2018, or within 30 days of hire if prior to October 1, 2018. The Facility Employee Training <br /> Certificate shall contain accurate information for all employees trained. <br /> CORRECTIVE ACTION: Update the Facility Employee Training Certificate to contain the accurate information and <br /> submit a copy of the updated form to the EHD. <br /> This is a repeat violation, Class Il. <br /> FA0003772 PR0232469 SCO01 05/18/2020 <br /> EHD 23-01 Rev.9/20/2019 Page 5 of 8 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />