Laserfiche WebLink
INDIVIDUAL TANK INFORMATION AND TEST RESULTS <br /> TEST DATE:04/28/04 8900 SHOAL CREEK,BUILDING 200 WORK ORDER NUMBER2230837 <br /> CLIENT:USA PETROLEUM AUSTIN,TEXAS 78757(512)451-6334 SITE:USA 835 <br /> Tank ID: 4 Tank manifolded: Bottom to top fill in inches: <br /> Product: DIESEL Vent manifolded: Bottom to grade in inches: <br /> Capacity in gallons: 4,108 Vapor recovery manifolded: Fill pipe length in inches: <br /> Diameter in inches: 96.00 Overfill protection: YES Fill pipe diameter in inches: <br /> Length in inches: 133 Overspill protection: YES Stage I vapor recovery: <br /> Material: DW STEEL Installed: ATG Stage II vapor recovery: <br /> CP installed on: <br /> COMMENTS <br /> Elm <br /> Dipped Water Level: Start(in) End(in) New/passed Failed/replaced New/passed Failed/replaced <br /> Dipped Product Level: L.D.#1 L.D.#1 L.D.#2 L.D.#2 <br /> Probe Water Level: Make: VAPORLESS <br /> Ingress Detected: Water Bubble Ullage Model: LD2000 <br /> Test time: S/N: 47236 <br /> Inclinometer reading: Open time in sec: 4.00 <br /> VacuTect Test Type: NOT Holding psi: 40 <br /> VacuTect Probe Ent <br /> ry Point: TESTED Resiliency cc: 170 NOT <br /> Test leak rate ml/m: 189.0 TESTED <br /> Pressure Set Point: Metering psi: 12 <br /> Tank water level in inches: Calib. leak in gph: 3.00 <br /> Water table depth in inches: Results: PASS <br /> Determined by(method): <br /> Result: COMMENTS <br /> COMMENTS <br /> mom <br /> Material: DW FIBERG <br /> Diameter(in): 2.0 <br /> Length (ft): 150.0 <br /> Test psi: 50 <br /> Bleedback cc: 155 <br /> Test time(min): 30 NOT NOT NOT <br /> Start time: 11:58 TESTED TESTED TESTED <br /> End time: 12:28 <br /> Final gph: 0.000 <br /> Result: PASS <br /> Pump type: PRESSURE <br /> Pump make: RED JACKET <br /> COMMENTS Impact Valves Operational: UNKNOWN <br /> Printed 05/04/2004 09:04 <br />