Laserfiche WebLink
�! 0 I Signed Original <br />TRACER TIGHT® TEST RESULTS g al <br />6/26/2003 <br />Shirley Environmental LLC Job No: 860208a <br />1928 Tyler Avenue, Suite K USA Petroleum #835 <br />South El Monte, CA 91733 2705 Country Club Blvd. <br />Stockton, CA 95204 <br />SYSTEM STATUS <br />SYSTEM# PRODUCT SIZE TRACER <br />Tank 1 Diesel 4,000 I NO <br />Premium 8,000 H OPEt3q. <br />D - <br />Unleaded 12,000 G V44B90 <br />Soil permeability is greater than 13.5 darcys. <br />GROUND WATER AND PRODUCT INFO <br />AT INOCULATION AT SAMPLING DEPTH FROM GRADE <br />06/09/03 06/16/03 WATER TANK TANK <br />TABLE BOTTOM TOP <br />SYSTEM# H2O PROD H2O PROD <br />(in) (in) (in) (in) (in) (in) (in) <br />Tank 1 0.00 50.00 0.00 61.00 96 147 51 <br />Tank 2 0.00 40.00 0.00 40.00 96 147 51 <br />Tank 3 0.00 45.00 0.00 65.00 96 147 51 <br />SITE COMMENTS <br />Backfill in tank pit consists of 1/4 to''/i inch pea gravel. Backfill in line trench consists of/e to''/z inch pea gravel and sand. <br />Ground cover over tanks and piping trench is concrete and asphalt. <br />TEST EVENTS <br />INSTALLATION <br />04/22/03 <br />FILL RISER — ! <br />INOCULATION <br />06/09/03 <br />SAMPLING <br />ST <br />PASS/F <br />Tank 1 Pass <br />Tank 2 Pass <br />Tank 3 Pass <br />ANALYSIS <br />06/23/03 <br />I declare under penalty of perjury that I am a licensed tank tester in the State of California and that <br />the information contained in this report is true and correct to the best of my knowledge. <br />Install/lnoculate---maearA CA Lic. No: (03-104 Signature Date I `03 <br />Sampler �� r— �� CA Lic. No: O 1- � C9 4 3 Signature ` Date 0-7-- 'a <br />TRC Analyst Gt r✓ H .SC� C n MPV 6' CA Lic. No: q3 - IS`& O Signature d Date 0:3 <br />