Laserfiche WebLink
Form I <br /> Source Test Results <br /> Static Leak Test <br /> Date: 09/18/2002 Time: 08:30 Application No. N-748 <br /> GDF Name and address: 20632 4627 DA VINCI DR. <br /> Stage II system(check one): Vapor Balance [ ] Single Hose M.P.D. [X ] <br /> Vacuum Assist [X ] Type: VAPOR VAC <br /> Stage I type(check one): Two point [X ] Manifolded? Yes [X ] <br /> Coaxial [ ] No [ ] <br /> Tank# 1 2 <br /> Product grade re alar prendum <br /> Actual tank capacity(gallons) 10028 10028 20056 <br /> Gasoline volume(gallons) 5674 5555 11229 <br /> Ullage(gallons) 4354 4473 8827 <br /> Initial pressure of UST,inches H2O 2 2 <br /> Number of nozzles served by tank 4 4 <br /> Test location: (A)Stage I vapor <br /> coupler of(B) Stage H riser a <br /> Initial Pressure,inches H2O(2.0) 2 <br /> Pressure after 1 min. (inches H2O) 1.98 <br /> Pressure after 2 min. (inches H2O) 1.96 <br /> Pressure after 3 min. (inches H2O) 1.95 <br /> Pressure after 4 min. (inches H2O) 1.94 <br /> Final Pressure after 5 min. (inches <br /> H2O) 1.93 <br /> Allowable Final Pressure: Table IA, <br /> Table 1B,Equations 9.1, 9.2 1.89 <br /> Test Status [Pass or Fail] Pass <br /> Tests Conducted By: MLEVESQUE <br /> Test Company: TANKNOLOGY Date of Tests: 09/18/2002 <br /> Tests Witnessed By: Tom <br /> GENSH-Rev 8/7/2002 Work Order#: 2223783 <br />