HUNTER ENVIRONMENTAL SERVICES, INC. FINAL TEST RESULTS <br />597 CENTER AVENUE, SUITE 350 TEST DATE: 3/7/89 <br />MARTINEZ, CA 94553 <br />1-800-321-3637 <br />CUSTOMER: SHELL LOCATION/IDENTIFICATION NO.: 204-7524-3604 <br />ADDRESS: 2320 N. EL DORADO <br />STOCKTON, CA <br />TEST RESULTS SUMMARY <br />LEAK LOKATOR RESULTS <br />SYSTEM TANK SIZE WATER LEVEL ALR RECOMMEN- <br />NO PRODUCT GALLONS DIA/MATL INCHES INCHES GPH CONCLUSION DATIONS <br />1 SUPER 8,000 <br />95 <br />1 <br />158 -.022 <br />TIGHT <br />2 U/L 8,000 <br />95 <br />0 <br />162 -.035 <br />TIGHT <br />3 REG 10,000 <br />95 <br />0 <br />160 -.016 <br />TIGHT <br />PRODUCT <br />LINES <br />- HYDROSTATIC <br />PRESSURE TEST <br />RESULTS <br />SYSTEM TYPE OF PUMP POUNDS POUNDS MINUTES PRODUCT PRODUCT CONCLUSION <br />NO PRODUCT REMOTE SUCTION APPLIED HELD HELD LOSS CC's LOSS GPH /RESULT <br />1 SUPER RJ <br />2 U/L RJ <br />3 REG RJ <br />50 50 15 <br />50 50 15 <br />50 50 15 <br />NOTE: On suction systems, NEVER put more than 15 psi on any pump system. <br />DETAIL OF TEST RESULTS <br />PASS <br />PASS <br />PASS <br />TEST <br />TIME <br />TEMPERATURE <br />ABSOLUTE <br />CHECK <br />SYSTEM TEST LEVEL <br />CLOCK DURATION LEAK RATE <br />COMPENSATION <br />LEAK RATE <br />TEST <br />NO PRODUCT NO (IN.) <br />START (HR -MIN) CC/DIV CC/MIN <br />DELTA OF CC/MIN <br />CC/MIN GPH <br />Y/N <br />1 SUPER <br />1 <br />158 <br />1:30 <br />1-0 <br />3.225 <br />+6.459 <br />+.023 <br />+7.892 <br />-1.433 <br />-.022 N <br />2 U/L <br />1 <br />162 <br />2:40 <br />1-0 <br />5.128 <br />-3.267 <br />-.003 <br />-.999 <br />-2.268 <br />-.035 N <br />3 REG <br />1 <br />160 <br />3:40 <br />1-0 <br />3.428 <br />+11.428 <br />+.030 <br />+12.495 <br />-1.067 <br />-.016 N <br />*LEVEL - Inches from Tank Bottom to Test Level <br />AIR - Absolute Leak Rate (Measured Leak Rate - Temperature Compensation) in Gallons <br />Per Hour. <br />CONCLUSION - NFPA 329 criterion of +/- 0.05 GPA is used to certify tightness. <br />This is to certify that the above tank systems were tested, using the HUNTER ENVIRONMENTAL <br />SERVICES, INC. LEAK LOKATOR according to all standard operating procedures. Those indicated <br />as tight at full system meet the criterion established by the National Fire Protection <br />Association Pamphlet 329 for Precision Testing. <br />Test Conducted By: Test Van No. 31 <br />Team Manager: STEVEN ANDERSON <br />Tank Testing Specialist: STEVEN PORRAS <br />Certification By: Pat Wheeler, Operations Manager <br />A:SHELL7524.RES <br />