Laserfiche WebLink
Ma'r,Gl 12 11:47a Elite IV Contactors 12094616342 p.4 <br />2. Preparing the tank for temporary closure <br />Blow back product lines. <br />Remove tank accessories, turbine, fill, vapor and inventory openir ?;s. <br />Gain access to tank for removal of liquid, solids, and sludge. Or.c : removed, will be placed <br />in hazmat drum on site with proper labeling and handled accordin J.y. <br />Tank cleaning procedure will be provided by Ramos Environmelt Ll Services <br />The tank will be rinsed with hot water and steam and also a biode, radable detergent. The <br />supply lines will be opened and flushed black to the tank prior tc i nsing. The reinstate will <br />be transported on a uniform hazardous waste manifest by Ramos 1 zzvironmental Services <br />California Contractors License # #808572 A, general and A Hz e: dorsement. <br />After the rinse, introduce 300 pound of dry ice to inert the tank an . verify that the tank has <br />been interted using an LEL meter. reference API 1604, section D Attached letter from <br />Ramos Environmental Services) <br />3. Checking LEL reading to make sure they are at safe levels: <br />Once safe levels have been achieved, lockable caps installed at all 3.ccess locations to tank, <br />except for required venting. <br />4. Owner and /or operator to daily check power on site and provide 1S print out. <br />Provide check list of a visual inspection of locks and or plugs dor ; on a weekly basis. <br />Owner and/or operator will need to inspect tank at least once ever three months to verify <br />that temporary closure measures are in proper place with Enviroln Cental Health Inspector. <br />Follow temporary closure Title 40 part 280 <br />