Laserfiche WebLink
0 AN. I I <br /> INDIVIDUAL TANK INFORMATION AND TEST RESULTS <br /> Ap y <br /> TEST DATE:10/18/99 8900 SHOAL CREEK,BUILDING 200 WORK ORDER NUMBER2210358 <br /> CL.IENT:ARCO PRODUCTS COMPANY AUSTIN,TEXAS 78757(512)451-6334 SITE:ARCO STATION #2130 <br /> TANK'!NE®RMA730N7 77 <br /> Tank ID: 87 #1 1 Tank manifolded: YES Bottom to top fill in inches: 174.5 <br /> Product: REG UNLEAD Vent manifolded: No Bottom to grade in inches: 181.5 <br /> Capacity in gallons: 10,369 Vapor recovery manifolded: YES Fill pipe length in inches: 54.5 <br /> Diameter in inches: 120.00 Overfill protection: YES Fill pipe diameter in inches: 4.0 <br /> Length in inches: 214 Overspill protection: YES Stage I vapor recovery: DUAL <br /> Material: DW FIBERG Installed: Stage II vapor recovery: BALANCE <br /> CP installed on: <br /> COMMENTS <br /> I'�0.1�K`'«'�2ES1��'�'��5i�eti3od'i7asTet , #' 2't�.S13ESt�Lt {.:`• , T`.,��.T :•�rtettlC►t ' A ��` : #' _ <br /> _ Start(in) End )(inNew/passed Failed/replaced New/passed Failed/replaced <br /> Dipped Water Level: 0.00 n) <br /> L.D.#1 L.D.#1 L.D.#2 L.D.#2 <br /> Dipped Product Level: <br /> 104.00 104.00 <br /> Probe Water Level: -0.003 0.000 Make: RED JACKET <br /> Ingress Detected: Water N Bubble N UllageN Model: CPT <br /> Test time: 10:07-12:03 S/N: <br /> Open time in sec: <br /> Inclinometer reading: 0.00 Holding psi: <br /> VacuTect Test Type: multiple tanks Resiliency cc: NOT <br /> VacuTect Probe Entry Point: Fill est leak rate ml/m: 189.0 TESTED <br /> Pressure Set Point: -0.50 Metering psi: 10 <br /> Tank water level in inches: 0.00 Calib. leak in gph: 3.00 <br /> Water table depth in inches: 190.00 Results: PASS <br /> Determined by(method): MONTR WELL <br /> Result: PASS COMMENTS <br /> COMMENTS <br /> IRA <br /> r HE' �`"�rTfl <br /> Material: DW FIBERG <br /> Diameter(in): 2.0 <br /> Length(ft): 150.0 <br /> Test psi: 50 <br /> Bleedback cc: 8o <br /> Test time(min): 30 NOT NOT NOT <br /> Start time: 11:00 TESTED TESTED TESTED <br /> End time: 11:30 <br /> Final gph: 0.014 <br /> Result: PASS <br /> Pump type: PRESSURE <br /> Pump make: RED JACKET <br /> COMMENTS Impact Valves Operational: YES <br /> Draft 10/20/1999 08:39 MSHAW <br />