VSFC Description and Component Locations VSFC Board <br />S1 DIP SWITCH SETTINGS <br />The S1 DIP switch settings are shown in Table 2 below. <br />Table 2: Setup Switch S1 <br />DIP Switch <br />Position -'ON' is up, `OFF' is down <br />1 <br />Off (default - DO NOT CHANGE!) <br />2 <br />Off (default - DO NOT CHANGE!) <br />3/4 <br />On/On = standalone (default), On/Off = alternate, Off/On = master/slave, Off/Off = Tank Based <br />5 <br />Off = slave, On = master (default) <br />6 <br />On = PLLD mode enabled (default), Off = disabled (mechanical LLD) <br />7 <br />On = Dry run retry disabled, Off = enabled (default) <br />8 <br />Off= Long handle warning enabled (2 hours), On = disabled (default) <br />S2 DIP SWITCH SETTINGS <br />The S2 DIP switch settings are shown in Table 3 below. <br />Table 3: Setup Switch S2 <br />DIP Switch <br />Position -'ON' is up, `OFF' is down <br />9 <br />On = 19200 UartO Baud, Off = 9600 UartO Baud (default - DO NOT CHANGE) <br />10 <br />Off = 9600 Uartl Baud, On = 19200 Uart1 Baud (default - DO NOT CHANGE) <br />11 <br />Off (default - DO NOT CHANGE!) <br />12 <br />Off (default - DO NOT CHANGE!) <br />13 <br />Off (default - DO NOT CHANGE!) <br />14 <br />Off (default - DO NOT CHANGE!) <br />15 <br />Off (default - DO NOT CHANGE!) <br />16 <br />Off (default - DO NOT CHANGE!) <br />SW1 ROTARY SWITCH SETTINGS <br />The S3 DIP switch settings are shown in Table 4 below. <br />QNOTE: Pressure should not be <br />set below 22 psi on The Red <br />Jacket pump or on other Red <br />Jacket pumps that have the <br />SwiftCheck or Spike Check <br />valve installed. <br />Table 4: Setup Switch SWI <br />SWI Position <br />Line Pressure (psi) <br />0 <br />14 <br />1 <br />16 <br />2 <br />18 <br />3 <br />20 <br />