Laserfiche WebLink
LINE <br />LEA%DETECTOR (LLD) TE!' REPORT <br />TEST DATE: August 23, 2006 <br />Al. FACILITY <br />Name Quik Stop Market # 39 <br />Address 2289 E. Fremont Street, Stockton, CA 95205 <br />Phone # 510-657-8500 <br />Contact Michael Karvelot <br />A2. OWNER <br />Name Quik Stop Markets, Inc. <br />Address 4567 Enterprise Street, Fremont, CA 94538 <br />Phone # 510-657-8500 <br />Contact Michael Karvelot <br />A3. C U P A <br />Name San Joaquin County Environmental Health <br />Address 304 E Weber Avenue, 3rd Floor, Stockton, CA 95202 <br />Notified August 8, 2006 <br />Inspector Toua Yang <br />Phone # 209-468-9847 <br />A4. TESTING CONTRACTOR <br />Name Walton Engineering, Inc. <br />Address P.O. Box 1025, W. Sacramento, CA 95691 <br />Lic # 617238 A, B, Haz <br />Contact Richard Walton <br />Phone # 916-825-3203 <br />I. MECHANICAL LINE LEAK DETECTOR TEST RESULTS <br />Test Equipment Used: Red Jacket FX Test System <br />Tank number 1 2 _ <br />Product contained Gasoline - 87 Gasoline - 91 <br />Leak detector make/model Vaporless LD -2000 Vaporless LD -2000 <br />I � <br />Serial number06 5041330 50615 <br />Resiliency (ml) <150 <150 <br />Opening time (seconds) 7 7 <br />Test leak rate (gph) 3.00 _ 3.00 <br />Functional Element Holding (psi) _ 30 _ _30_ <br />Metering pressure (psi) 20 _ 20 <br />Pump pressure (psi) 30 30 <br />TEST RESULT Pass Pass <br />Tank number _ <br />Product contained <br />Leak detector make/model <br />I <br />Serial number <br />Resiliency (ml) _ --- --_— _ <br />Opening time (seconds) <br />Test leak rate (gph) <br />Functional Element Holding (psi) <br />Metering pressure (psi) _ <br />Pump sure (psi) <br />TEST SRESULT-- <br />----------- - <br />J. COMMENTS: <br />WALTON <br />Signature: ENGSNEERING, INC. <br />Technician: Bruce N. Stewart / A31131 5249892 -UT Date: August 23, 2006 <br />v zuuo wairon engineering, Inc. <br />