Laserfiche WebLink
0 0 <br />Ouik Stop #39, 2285 E. Fremont, Stockton SR 0068255 <br />6. Qualified installers must possess or work under the direct and personal supervision of an <br />individual physically present at the work site who possesses all of the following: <br />a. A valid, current contractor's license issued by the Contractors State License Board, <br />and <br />b. A valid, current certificate of training from the manufacturer(s) of the component(s) <br />being installed, and <br />c. A valid, current UST Installation/Retrofitting certificate issued by the International <br />Code Council (ICC). <br />7. Log into the California Environmental Reporting System (CERS), complete and submit a <br />"UST Certification of Installation/Modification" form for the piping. <br />8. All components must be certified by an independent testing organization and labeled as <br />required by the organization (UL, ULC, ANSI, API, ASTM, etc.). See California Code of <br />Regulations (CCR) Title 23, Chapter 16, Table B for a complete list. <br />9. Permit expires 180 days from the date of approval. If an extension to the expiration date <br />is required, a written request must be submitted to this office prior to the expiration date. <br />If you have any further questions, please contact me at (209) 468-0335. <br />Thank you, <br />Jeffrey Wong, REHS <br />Senior Registered Environmental Health Specialist <br />1 <br />