Laserfiche WebLink
INDIVIDUAL TANK INFORMATION AND TEST RESULTS <br /> Tankirmlogy <br /> TEST DATE:07/17/02 8900 SHOAL CREEK,BUILDING 200 WORK ORDER NUMBER2223016 <br /> CLIENT:ULTRAMAR INC AUSTIN,TEXAS 78757(512)451-6334 SITE:ULTRAMAR 641 <br /> Tank ID: #1 1 Tank manifolded: No Bottom to top fill in inches: 192.0 <br /> Product: UNLEADED Vent manifolded: YES Bottom to grade in inches: 199.0 <br /> Capacity in gallons: 12,041 Vapor recovery manifolded: YES Fill pipe length in inches: 64.0 <br /> Diameter in inches: 128.00 Overfill protection: YES Fill pipe diameter in inches: 4.0 <br /> Length in inches: 218 Overspill protection: YES Stage I vapor recovery: DUAL <br /> Material: DW STEEL Installed: ATG Stage 11 vapor recovery: ASSIST <br /> CP installed on: <br /> COMMENTS <br /> Dipped Water Level: Start(in) End(in) New/passed Failed/replaced New/passed Failed/replaced <br /> Dipped Product Level: L.D.#1 L.D.#1 L.D.#2 L.D.#2 <br /> Probe Water Level: Make: RED JACKET <br /> Ingress Detected: Water Bubble Ullage Model: Fx1V <br /> Test time: S/N: 40601-9364 <br /> Inclinometer reading: Open time in sec: <br /> Holding psi: 12 <br /> VacuTect Test Type: NOT Resiliency in ml: 12 NOT <br /> VacuTect Probe Entry Point: TESTED TESTED <br /> Test leak rate ml/m: 189.o <br /> Pressure Set Point: Metering psi: <br /> Tank water level in inches: Calib. leak in gph: 3.00 <br /> Water table depth in inches: Results: FAIL <br /> Determined by(method): <br /> Result: <br /> COMMENTS <br /> COMMENTS <br /> Material: DW FIBERG <br /> Diameter(in): 2.0 <br /> Length(ft): 100.0 <br /> Test psi: 60 <br /> Bleedback cc: 40 <br /> Test time(min): 30 NOT NOT NOT <br /> Start time: 10:52 TESTED TESTED TESTED <br /> End time: 11:22 <br /> Final gph: 0.003 <br /> Result: PASS <br /> Pump type: PRESSURE <br /> Pump make: RED JACKET <br /> COMMENTS Impact Valves Operational: YES <br /> Printed 07/18/2002 17:22 <br />